1SDH000510R0001
20/28
Page N.
L2388
EP010
ABB SACE
Not applicable
BINARY OUTPUT
Number of variables 0
Number of bytes 0
#
Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
PR123 only
[bytes]
default
0 Maximum current
Not available | <0.05In |
A
2^32-1|0|1|16ln
2
Most Significant
{lmin ... lmax}
| > 16ln
Word
1 L1 run time current
Not available | <0.05In |
A
2^32-1|0|1|16ln
2
Least Significant
{lmin ... lmax}
| > 16ln
Word
2 L2 run time current
Not available | <0.05In |
A
2^32-1|0|1|16ln
2
Least Significant
{lmin ... lmax}
| > 16ln
Word
3 L3 run time current
Not available | <0.05In |
A
2^32-1|0|1|16ln
2
Least Significant
{lmin ... lmax}
| > 16ln
Word
4 N run time current
Not available | <0.05In |
A
2^32-1|0|1|16ln
2
Least Significant
{lmin ... lmax}
| > 16ln
Word
5 Internal Rog Ground run time current Not available | <0.05In | 1
A
2^32-1| 0 | 1|
2
Least Significant
Word
6 V0 residual voltage
Not available | >1.6V |
V
10
2^16-1 | 0 | V |
2
{1.6 ... 150*SQRT(3)}
| >
150*SQRT(3)
150*SQRT(3)
7 V12 line to line voltage
Not available | >1.6V |
V
10
2^16-1 | 0 | V |
2
{1.6 ... 150*SQRT(3)}
| >
150*SQRT(3)
150*SQRT(3)
8 V23 line to line voltage
Not available | >1.6V |
V
10
2^16-1 | 0 | V |
2
{1.6 ... 150*SQRT(3)}
| >
150*SQRT(3)
150*SQRT(3)
9 V31 line to line voltage
Not available | >1.6V |
V
10
2^16-1 | 0 | V |
2
{1.6 ... 150*SQRT(3)}
| >
150*SQRT(3)
150*SQRT(3)
10 Total active power
Not available||P|<(0.1In*1.6V)|
kW
10
2^3-1 | 0 | P
4
2 words (signed)
{(0.1In*1.6V)...(16In*150*
SQRT(3))} |
> (16In*150*SQRT(3)) | <
(16In*150*SQRT(3))|
-(16In*150*SQRT(3))
-(16In*150*SQRT(3))
Format: Low Word |
High Word
11 Total reactive power
Not available||P|<(0.1In*1.6V)|
kVAR
10
2^3-1 | 0 | P
4
2 words (signed)
{(0.1In*1.6V)...(16In*150*
SQRT(3))}|
> (16In*150*SQRT(3)) | <
(16In*150*SQRT(3))|
-(16In*150*SQRT(3))
-(16In*150*SQRT(3))
Format: Low Word |
High Word
ANALOG INPUT
Number of variables 14
Number of bytes 32
# Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
PR123 only
[bytes]
default
1 (Acyclic) Command info:
2
0
byte 0-1: command value
No command|CB Open|CB Close|
0 | 1 | 2 | 3 |
2
0
CB reset | Trip Reset |
4 | 5 | 6 | 7 |
Reset Signalling |
8 | 9 | 10
Reset history measurements |
Reset energy counters |
Reset Events log|Restart trigger
Datalogger | Stop Datalogger
byte 2-3:
Don’t care
2
0
2
Slave ID
2
Yes
3
SW version
MM.mm
MSB = MM
2
Yes
LSB = mm
PARAMETERS
Number of parameters 233
Number of bytes 512
#
Name/Description
Range
Units
Multipler
Coding
Lenght
Range
Notes
[bytes]
default
0
(Cyclic) Command info - value
No command|CB Open|CB Close|CB Reset |
0 | 1 | 2 | 3 | 4 | 5
2
0
Trip Reset | Reset Signalling
6 | 7 | 8 | 9 | 10
Reset history measurements |
Reset energy counters |
Reset Events log | restart trigger Datalogger |
Stop Datalogger
1 (Cyclic) Command info - parameter
Don’t care
ANALOG INPUT
Number of variables 2
Number of bytes 4