Table 8
RELT
: It requires a dedicated RELT-Signaling 2K-3 Relt blu switch “GTUTRSK”
1SDHO01000R0524
IGF
: will require NCT adapter
1SDHO01000R0530
Zone selectivity
: Reuse of external existing wiring by rewiring the internal ZSi, “Legacy
zone selectivity is
not compatible with Emax2
. In case the functions is used, it is necessary
to replace all legacy breakers connected with Emaxe retrofill”
1SDCO007100G0205
Dialogue Module
: “ Emax2 offers multiple communication modules, like Ekip Com Modbus
TCP, Ekip Com EtherNet/IP™, Ekip Com Profinet, Ekip Com IEC 61850, Ekip Com
Modbus RTU, Ekip Com Profibus DP, Ekip Com DeviceNet™; integration with
Emax2 integrated
communication modules with different protocols requires the
adaptation of existing supervision system to accept new connections with dedicated
new system interfaces refer the following document for details
1SDH001140R00001
C