The activation of local bus — essential to start the communication between the module
and the Trip unit
35 - Synchronizing 2K-1 signalling module with the trip unit
Figure 66
Figure 67
Off: module off
Fixed or flashing light synchronized on power LED of Ekip Touch: module ON and
communication with Trip unit present
Flashing not synchronized with power LED of Ekip Touch (two fast flashes per second):
module ON and communication with Trip unit absent
If the Ekip Signalling 2K module is detected correctly by Ekip Touch the specific
configuration area in the Modules Settings menu is activated.
For each Ekip Signalling 2K module detected by Ekip Touch, a specific menu is available
containing the submenus of all the available and configurable inputs and outputs.
Power LED reports ON status and correct communication with Ekip Touch :
Once the local bus is activated 2k modue should synchronize with the Ekip touch trip
unit.
Check the following for synchronization status.
C