6 - Related Publications
7 - Service and Support
8 - Estimated Time to Complete Tasks
Service and support are available from ABB Inc USA.
Email: [email protected]
Phone: 888-385-1221
Verify the secondary disconnects and match the switchgear cublicle which may take up to
1Hr depending on the complexity of the original breaker. Once the retrofill breaker is fully
prepared, it should take about 20 minutes to swap out the old breaker and rack in the new
Emax 2 Retrofill circuit breaker if the proper lifting bar and hoist are available, it may take an
additional 30 min to replace the door.
The Emax 2 Retrofill, when ordered with 4 wire ground fault, will be equipped with a Neutral
CT adapter. The adapter will modify the GE MicroVersaTrip type Neutral CT output to a
Rogowski sensor output compatible with the Emax 2 Retrofill Trip Unit. With this device, it
will not be necessary to change the neutral CT in the switchgear to a Rogowski sensor.
Title
Publication
Publication Number
Accessory: Neutral CT Adapters Installation Instructions
Accessory: Programmer Disconnects Installation Instructions
Accessory: Primary Disconnects Installation Instructions
Accessory: Secondary Disconnects, Installation Instructions
E2.2, 4.2, 6.2 Breakers Installation, Operation & Maintenance Manual
Instructions for using Ekip touch protection releases & accessories
Emax 2 Family Trip units Engineering manual
Installation Manual AKD 10
Installation Manual AKD 8
Installation Manual AKD 6
Installation Manual AKD 5
Accessory: Door Interlock (Door Interlock Kit)
Accessory: Kirk Key installation Manual
Accessory Retrofill Direct Replacement / CiC Full Door Kits AKD-5, 6, 8 & 10
Accessory Retrofill Direct Replacement / CiC Door AdaptorsKits AKD-5, 6, 8 &10
Accessory OEM Direct Replacement Adaptor kits AKD8 & 10
Accessory OEM Direct Replacement Adaptor kits, AKD8 &10, AKR 75/100, B&F TYPE
Accessory OEM Direct Replacement Adaptor kits, AKD8 &10, only for AKR30S
Accessory: Position Switch Plate, Assembly & Wiring
Accessory: Neutral CT Adapters Installation Instructions
Accessory: Programmer Disconnects Installation Instructions
Accessory: Primary Disconnects Installation Instructions
Accessory: Secondary Disconnects, Installation Instructions
E2.2, 4.2, 6.2 Breakers Installation, Operation & Maintenance Manual
Instructions for using Ekip touch protection releases & accessories
Emax 2 Family Trip units Engineering manual
2TSA451010P0000
2TSA451009P0000
2TSA451014P0000
2TSA451011P0000
2TSA451017P0000
2TSA451013P0000
2TSA451007P0000
2TSA451008P0000
2TSA431967R1000
2TSA431968R1000
2TSA431996R1000
2TSA451019P0000
2TSA451018P0000
2TSA451012P0000
2TSA451015P0000
2TSA451016P0000
1SDH001000R0002
1SDH001316R0002
1SDH001330R0002
C
Summary of Contents for Emax 2 Retrofill
Page 36: ...11 14 22 21 31 34 42 41 C2 C1 51 54 62 61 71 74 82 81 91 94 02 01 45 48 R1 R2 C ...
Page 38: ...C ...
Page 43: ...NOTES 1 WP WavePro fixed connection point C ...
Page 51: ...ONLY for 3200A Figure 48 Steps in Exploded Views for 3200A WPS 32 WPH 32 WPX 32 C ...
Page 52: ...ONLY for 3200A Figure 49 Steps in Exploded Views for 4000A WPS 40 WPX 40 C ...
Page 53: ...Figure 50 Steps in Exploded Views for 5000A WPS 50 WPX 50 ONLY for 3200A C ...
Page 65: ...Figure 64 Wiring of WP 4000A breaker with FAN control unit C ...
Page 74: ...Figure 75 Figure 76 WPF 16 with special 2500A Fuse WPF 16 2500A Fuse Tang Positions 74 C ...