94
Service
3ADW000488R0101 DCS880 Service manual e a
Exchange cooling fan size H4
Before the work is started, disconnect the thyristor power controller completely from the
power supply, then check the voltage free condition and make sure, everything is located
in an electrical and mechanical safe condition!
Unit sizes DCS880-S0b-0610-dd ...
DCS880-S0b-1000-dd using either one 230
V
AC
or one 115 V
AC
fan.
Removing the converter fan
1. Remove the control panel, the design
cover and the fan connection plug X52 on
the top of the converter housing.