113
Service
3ADW000488R0101 DCS880 Service manual e a
Set type code
The type code - 95.25 Set: Type code - is preset in the factory and is write protected. It identifies the drives
current-, voltage-, temperature measurement and its quadrant type. The type code can only be changed as
whole or individually.
To change the type code as whole use the control panel and follow the instructions below:
−
Un-protect the type code by means of 95.24 Service mode = Set: Type code.
−
95.25 Set: Type code = S01-0020-04 … S02-5200-05 (details, see table below).
The drive’s basic type code:
DCS880-aab-cccc-ddef
Product family:
DCS880
Product type:
aa
= S0 Standard converter module
= R0 Rebuild kit
= E0 Panel solution
= A0 Enclosed converter
Bridge type:
b
= 1
Single bridge (2-Q)
= 2
2 anti-parallel bridges (4-Q)
Module type:
cccc
=
Rated DC current (IP00)
Rated AC voltage: dd
= 04
100 V
AC
… 415 V
AC
= 05
100 V
AC
… 525 V
AC
= 06
270 V
AC
… 600 V
AC
= 07
315 V
AC
… 690 V
AC
= 08
360 V
AC
… 800 V
AC
= 10
450 V
AC
… 990 V
AC
= 12
540 V
AC
… 1200 V
AC
Power connection: e
= X
Standard H1 … H7
= L
Left side H8
= R
Right side H8
Revision code:
f
= 0
1
st
generation
Attention:
When using H1 … H5 modules the current and voltage range of the type code setting is limited to
max 1190 A
DC
and max 600 V
AC
.
−
The change of the type code is immediately taken over and 95.24 Service mode is automatically set back to
Normal mode.
−
The new values can be seen in group 7:
−
07.34 Drive block bridge 2 set.
−
07.35 Drive DC current scaling set.
−
07.37 Drive AC voltage scaling set.
−
07.38 Drive max bridge temperature set.
To change the type code individually use the control panel and follow the instructions below:
−
Un-protect the type code by means of 95.24 Service mode = Set: Type code.
−
Set the type code individually by means of:
−
95.26 Set: Drive block bridge 2.
−
95.27 Set: Drive DC current scaling.
−
95.28 Set: Drive AC voltage scaling.
−
95.29 Set: Drive max bridge temperature.
The change of the type code is immediately taken over and 95.24 Service mode has to be set back to Normal
mode by the user.
−
The new values can be seen in group 7:
−
07.34 Drive block bridge 2 set.
−
07.35 Drive DC current scaling set.
−
07.37 Drive AC voltage scaling set.
−
07.38 Drive max bridge temperature set.