Voltage ripple of voltage U
DC
depending on operation modes.
DCSLink communication
The field converter is controlled from armature converter via DCSLink based on CAN hardware.
Node address is set by:
S800 digit 0 (node address 00 is not possible!).
S801 digit 10.
Same node address must be selected in the corresponding armature converter.
Example: Node address = 13 ==> S800 = 3 and S801 = 1.
The communication speed is set by S1100.
S1100:6 S1100:5 S1100:4 Baudrate
[kBaud]
Selection in armature converter,
parameter (94.02)
OFF
OFF
OFF
20
0
OFF
OFF
ON
50
1
OFF
ON OFF
125
2
OFF
ON
ON
250
3
ON
OFF
OFF
500
4
ON
OFF
ON
800
5
ON
ON
OFF
888
6
ON
ON
ON
1000
7
DZ_LIN_014_Spg-well_a.ai
V
oltage r
ipple
Vsec
U
DC
Field
Single-phase, half-controlled
3
-phase, half-controlled
3
-phase, full-controlled
1
0.75
0.5
0.25
0
0.1
0.4
0.7
1
X1:1
2
SF_FEX4_002_DCSLink_a.dsf
X
3
:1
2
3
24 V / 200 mA
S
1100:1
CANL
CANH
S
1100:3
GNDB
S
1100:2
SDCS-FEX-4
Termination 200 kOhm
Incoming power
Remarks
24 V
200 mA
24 V grounded via X51 of SDCS-DSL-H1x
DSL communication
Remarks
Bus termination
S1100:
1 = ON
120 Ohm
1 = OFF
No termination
Ground termination
S1100:
2 = ON
200 kOhm R-C ground termination
3 = ON
0 Ohm ground termination
2, 3 = OFF
No termination