Planning the electrical installation
47
3ADW000462R0401 DCS880 Hardware manual e d
For compliance with the protection objectives of the
German EMC Act (EMVG) in systems and
machines, the following EMC standards must be
satisfied:
For emitted interference, the following apply:
EN 61000-6-3
Specialised basic standard for emissions in
light industry
can
be satisfied with special features (mains filters, screened power
cables) in the lower rating range *(EN 50081-1).
EN 61000-6-4
Specialised basic standard for emissions in
industry
*(EN 50081-2).
For interference immunity, the following apply:
EN 61000-6-1
Specialised basic standard for interference immunity in
residential areas
*(EN 50082-1).
EN 61000-6-2
Specialised basic standard for interference immunity in
industry
.
If this standard is satisfied, then the EN 61000-6-1 standard is
automatically satisfied as well *(EN 50082-2).
* The old generic standards are given in brackets
Product Standard EN 61800-3
EMC
standard for drive systems (
P
ower
D
rive
S
ys-
tem), interference immunity and emissions in resi-
dential areas, enterprise zones with light industry
and in industrial facilities.
This standard must be complied with in the EU for
satisfying the EMC requirements for systems and
machines!
Standards
Second environment
(industry) with PDS categories C3, C4
EN 61800-3
Not applicable
EN 61000-6-3
Satisfied
On customer's request
Satisfied
EN 61000-6-4
Satisfied
EN 61000-6-2
EN 61000-6-1
PDS category C3
PDS category C4
Classification
The following overview uti-
lises the terminology and
indicates the action
required in accordance with
Product Standard
EN 61800-3
For the DCS880 series, the
limit values for emitted
interference are complied
with, provided the measure
indicated is carried out.
PDS of category C2 (for-
merly restricted distribution
in first environment) is
intended to be installed and
commissioned only by a
professional (person or
organization with necessary
skills in installing and/or
commissioning PDS includ-
ing their EMC aspects).
For power converters with-
out additional components,
the following warning
applies:
This is a product of cate-
gory C2 under IEC 61800-
3:2004. In a domestic/res-
idential environment this
product may cause radio
interference in which
case supplementary miti-
gation measures my be
required.
The field supply is not
depicted in this overview
diagram. For the field cur-
rent cables, the same rules
apply as for the armature-
circuit cables.
M
M
M
M
M
M
I
DC
< 100 A
I
DC
< 100 A
I
DC
>100 A
Supply transformer for a
residential area (rating
normally
≤
1.2 MVA)
Earthed 400 V network
with neutral conductor ;
3
~
≤
400 A
Operation at low-voltage network together with
other loads of all kinds, apart from some kinds
of sensitive communication equipment.
T
o
other loads
, e
.g.
dr
iv
e systems
Line r
Y-capacitor
Line reactor
Converter
Converter
Mains filter
Earthed
neutral
Medium-voltage network
Industrial zone
alter
nativ
e
alter
nativ
e
Line reactor
Converter
alter
nativ
e
Comm
utation notches < 40
%
M
M
M
M
SB_
8
00_004_emv-classif_a.ai
Converter
transformer
Case-ref
erenced EMC analysis
alter
nativ
e
Converter
transformer
with earthed
iron core
(and earthed
screen where
appropriate)
alter
nativ
e
I > 400 A
and / or
U > 500 V
Operation with separate power converter transformer. If there
are other loads at the same secondary winding, these must be
able to cope with the commutation gaps caused by the power
converter. In some cases, commutating reactors will be
required.
T
o
other loads
, e
.g.
dr
iv
e systems
Converter
Converter
Line reactor
Medium-voltage network
Industrial
zone
Legend
Unscreened cable with restriction
Screened cable