Mechanical installation
22
3ADW000462R0301 DCS880 Hardware Manual e c
Before installation
Install the drive in an upright position with the cooling section facing a wall. Check
the installation site according to the requirements below. Refer to chapter
for frame details.
Requirements for the installation site
See chapter
for the allowed operation conditions of the drive.
Wall
The wall should be as close to vertical as possible, of non-flammable material and
strong enough to carry the weight of the unit. Check that there is nothing on the wall
to inhibit the installation.
Floor
The floor or material below the installation should be non-flammable.
Free space around the unit
Around the unit free space is required to enable cooling airflow, service and
maintenance see chapter
.
Cabinet installation
The required distance between parallel units is five millimetres (0.2 in.) in
installations without the front cover. The cooling air entering the unit must not exceed
+40 °C
(+104 °F).
Preventing cooling air recirculation
Unit above another
Prevent air recirculation inside and outside the cabinet.
Lead the exhaust cooling air away from the unit above.
Distances see chapter
BG_800_004_luft_a.ai
Hot area
Cool area
Main air flow in
Air baffle plates
Main air flow out
max.+40 °C
BG_800_003_luft_a.ai
Air baffle plate
Airflow