Technical data
69
3ADW000194R0611 DCS800 Hardware Manual f us
Technical data
What this chapter contains
This chapter contains the technical specifications of the drive, e.g. the ratings, sizes
and technical requirements, provisions for fulfilling the requirements for CE and
other markings and warranty policy.
Reference:
Hardware extension
RAIO Analog I/O Extension
publ.no.:3AFE64484567
Hardware extension
RDIO Digital I/O Extension
publ.no.:3AFE64485733
DCS800 1131 Programming target
publ.no.:3ADW000199
Branching units NDBU-95
publ.no.:3ADW000100
Environmental Conditions
System connection
Environmental limit values
Voltage, 3-phase:
230 to
≤
1000 V acc. to IEC 60038
Permissible cooling air temp.
Voltage deviation:
±10% continuous; ±15% short-time *
- at converter module air inlet:
0 to +55°C
Rated frequency:
50 Hz or 60 Hz
with rated DC current:
0 to +40°C
Static frequency deviation:
50 Hz ±2 %; 60 Hz ±2 %
w. different DC curr. acc. Fig.
below:
+30 to +55°C
Dynamic: frequency range:
50 Hz: ±5 Hz; 60 Hz: ± 5 Hz
- Options:
0 to +40°C
df/dt:
17 % / s
Relative humidity (at 5...+40°C):
5 to 95%, no condensation
* = 0.5 to 30 cycles.
Relative humidity (at 0...+5°C):
5 to 50%, no condensation
Please note
: Special consideration must be taken for voltage devi-
ation in regenerative mode.
Change of the ambient temp.:
< 0.5°C / minute
Degree of protection
Storage temperature:
-40 to +55°C
Converter Module and
options (line chokes, fuse
holder,
Transport temperature:
Pollution degree (IEC 60664-1,
IEC 60439-1):
-40 to +70°C
2
field supply unit, etc.):
IP 00 / NEMA TYPE OPEN
Vibration class
3M3 - D1...D4
Enclosed converters:
IP 20/21/31/41
(IEC-60721-3-3)
3M1 - D5...D7
Paint finish
Site elevation
Converter module:
light grey RAL 9002
<1000 m above M.S.L.:
100%, without current reduction
Enclosed converter:
light grey RAL 7035
>1000 m above M.S.L.:
with curr. reduct., see Fig. below
Size
Sound pressure level L
P
(1 m dis-
tance)
Vibration
Shock
Transport in
original Package
Short circuit withstand rating
The DCS800 is suitable for use in a circuit capa-
ble of delivering not more than:
as module
enclosed conv.
as module
D1
55 dBA
54 dBA
1.5 mm, 2...9 Hz
0.5 g, 9...200 Hz
7 g / 22 ms
1.2 m
65 kA rms symmetrical amps at maximum
600 VAC
D2
55 dBA
55 dBA
D3
60 dBA
73 dBA
1.0 m
D4
66...70 dBA,
depending on fan
77 dBA
D5
73 dBA
78 dBA
0.3 mm, 2...9 Hz
0.1 g, 9...200 Hz
4 g / 22 ms
0.25 m
Shock monitor
100 kA rms symmetrical amps at maxi-
mum 600 VAC
D6
75 dBA
73 dBA
D7
82 dBA
80 dBA
Effect of the site elevation above sea level on the converter’s load capacity
Current reduction to (%)
Effect of the ambient temperature on the converter module load capacity
Current reduction to (%) for converter modules
50
60
70
80
90
100
1000
2000
3000
4000
5000
m
70
80
90
100
110
30
35
40
45
50
55°C
Summary of Contents for DCS800
Page 1: ...DCS800 Hardware Manual DCS800 Drives 20 to 5200 A ...
Page 4: ...3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 20: ...The DCS800 20 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 54: ...Planning the electrical installation 54 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 66: ...Installation checklist 66 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 104: ...Technical data 104 3ADW000194R0611 DCS800 Hardware Manual f us ...