Electrical installation
61
3ADW000194R0611 DCS800 Hardware Manual f us
The maximum distance between pulse encoder and interface board is dependent on
the voltage drop on the connecting lines and on the output and input configuration of
the used components. If cables are used according to the table below the voltage
drop caused by the cable can be compensated by the voltage regulator.
Use twisted pair cable with pair shielding plus overall shielding.
Cable length
parallel wires for
power source & GND
Cable used
0 ... 50 m
1x 0.25 mm²
12x 0.25 mm²
50 ... 100 m
2x 0.25 mm²
12x 0.25 mm²
100 ... 150 m
3x 0.25 mm²
14x 0.25 mm²
Cable length
parallel wires for
power source & GND
Cable used
0 to 164 ft
1 x 24 AWG
12 x 24 AWG
164 to 328 ft
2 x 24 AWG
12 x 24 AWG
328 to 492 ft
3 x 24 AWG
14 x 24 AWG