Planning the electrical installation
33
3ADW000194R0611 DCS800 Hardware Manual f us
Semiconductor type F1 fuses and fuse holders for AC and DC power lines
(DCS800-S01 / DCS800-S02)
The converter units are subdivided into two groups:
•
Unit sizes D1, D2, D3 and D4 with rated currents up to 1000 A require external
fuses.
•
In unit sizes D5, D6 and D7 with rated currents of 900 A to 5200 A, the branch
semiconductor fuses are installed internally (no additional external semiconductor
fuses are needed).
The third column of the table below assigns the AC fuse type to the converter type.
In case the converter should be equipped with DC fuses according to the hints, use
the same type of fuse as on AC side at DC side (C1, D1). Blade type fuses are used
for all the converters construction type D1...D4 except the converters
(610 A, 680 A, 740 A, 820 A, 900 A, 1000 A).
Fuses and fuse holders (details see chapter
Technical Data
)
Note 1: No fuse holder is available. Attach fuses directly to busbar.
Fuses F3.x and fuse holders for field supply
Depending on the protection strategy different types of fuses are to be used. The
fuses are sized according to the nominal current of the field supply device. If the field
supply unit is connected to two phases of the network, two fuses should be used; in
case the unit is connected to one phase and neutral only one fuse at the phase can
be used. Table below lists the fuse currents with respect to the table above.
The fuses can be sized according to the maximum field current. In this case take the
fuse, which fits to the rated field current levels.
Type of converter
Size
Fuse type
Fuse holder
Type
Fuse Holder
2-Q Converter
4-Q Converter
North America
DCS800-S01-0020-04/05
DCS800-S02-0025-04/05
D1
170M 1564
OFAX 00 S3L
FWP-50B
1BS101
DCS800-S01-0045-04/05
DCS800-S02-0050-04/05
170M 1565
OFAX 00 S3L
FWP-80B
1BS101
DCS800-S01-0065-04/05
DCS800-S02-0075-04/05
170M 1568
OFAX 00 S3L
FWP-125A
1BS103
DCS800-S01-0090-04/05
DCS800-S02-0100-04/05
170M 1568
OFAX 00 S3L
FWP-125A
1BS103
DCS800-S01-0125-04/05
DCS800-S02-0140-04/05
170M 3815
OFAX 1 S3
FWP-200A
1BS103
DCS800-S01-0180-04/05
DCS800-S02-0200-04/05
D2
170M 3816
OFAX 1 S3
FWP-250A
1BS103
DCS800-S01-0230-04/05
DCS800-S02-0260-04/05
170M 3817
OFAX 1 S3
FWP-300A
1BS103
DCS800-S01-0315-04/05
DCS800-S02-0350-04/05
D3
170M 5810
OFAX 2 S3
FWP-500A
1BS103
DCS800-S01-0405-04/05
DCS800-S02-0450-04/05
170M 6811
OFAX 3 S3
FWP-700A
See Note 1
DCS800-S01-0470-04/05
DCS800-S02-0520-04/05
170M 6811
OFAX 3 S3
FWP-700A
See Note 1
DCS800-S01-0610-04/05
DCS800-S02-0680-04/05
D4
170M 6163
3x 170H 3006
FWP-900A
See Note 1
DCS800-S01-0740-04/05
DCS800-S02-0820-04/05
170M 6163
3x 170H 3006
FWP-900A
See Note 1
DCS800-S01-0900-04/05
DCS800-S02-1000-04/05
170M 6166
3x 170H 3006
FWP-1200A
See Note 1
DCS800-S01-0290-06
DCS800-S02-0320-06
D3
170M 5810
OFAX 2 S3
FWP-500A
See Note 1
DCS800-S01-0590-06
DCS800-S02-0650-06
D4
170M 6813
OFAX 3 S3
FWP-900A
See Note 1
Summary of Contents for DCS800
Page 1: ...DCS800 Hardware Manual DCS800 Drives 20 to 5200 A ...
Page 4: ...3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 20: ...The DCS800 20 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 54: ...Planning the electrical installation 54 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 66: ...Installation checklist 66 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 104: ...Technical data 104 3ADW000194R0611 DCS800 Hardware Manual f us ...