Planning the electrical installation
52
3ADW000194R0611 DCS800 Hardware Manual f us
Selecting the control cables
All control cables except 220 V or 115 V must be shielded.
Use a double-shielded twisted pair cable (Figure a, e.g. JAMAK by NK Cables,
Finland or BELDEN type, USA) for analogue signals. This type of cable is
recommended for the pulse encoder signals also. Employ one individually shielded
pair for each signal. Do not use common return for different analogue signals.
A double-shielded cable is the best alternative for low-voltage digital signals but
single-shielded twisted multipair cable (Figure b) is also usable.
Run analogue and digital signals in separate, shielded cables.
Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in
the same cables as digital input signals. It is recommended that the relay-controlled
signals be run as twisted pairs.
!
Never mix 24 VDC and 115/230 VAC signals in the same cable
.
DCS800 panel cable
The cable connection of the DCS800 panel to the drive must not exceed 3 meters
(10 ft). The cable type tested and approved by ABB is used in control panel option
kits.
a
A double-shielded twisted
pair cable
b
A single-shielded twisted
multipair cable
Summary of Contents for DCS800
Page 1: ...DCS800 Hardware Manual DCS800 Drives 20 to 5200 A ...
Page 4: ...3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 20: ...The DCS800 20 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 54: ...Planning the electrical installation 54 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 66: ...Installation checklist 66 3ADW000194R0611 DCS800 Hardware Manual f us ...
Page 104: ...Technical data 104 3ADW000194R0611 DCS800 Hardware Manual f us ...