background image

7

41-181.2K

current through the trip circuit to close the contacts of
the ICS. This value of current should be not greater
than the particular ICS tap setting being used. The
operation indicator target should drop freely.

The contact gap should be approximately .047”
between the bridging moving contact and the station-
ary contacts. The bridging moving contact should
touch the stationary contacts simultaneously.

7.1.3.2.

AC Indicating Contactor Switch (ACS)

Close the main relay contacts and pass sufficient ac
current through the trip circuit to close the contacts of
the ACS. This value of current should be not greater
than the particular ACS rated operating current being
used. The operation indicator target should drop
freely.

The contact gap should be approximately 3/32”
between the bridging contact and the adjustable sta-
tionary contacts. The bridging moving should touch
both stationary contacts simultaneously.

7.2. ROUTINE MAINTENANCE

All relays should be inspected periodically and the
time of operation should be checked at least once
every year or at such other time intervals as may be
dictated by experience to be suitable to the particular
application. Phantom loads should not be used in
testing induction-type relays because of the resulting
distorted current wave form which produces an error
in timing.

All contacts should be periodically cleaned. A contact
burnisher style #182A836H01 is recommended for
this purpose. The use of abrasive material for clean-
ing contacts is not recommended, because of the
danger of embedding small particles in the face of
the soft silver and thus impairing the contact.

8.0

CALIBRATION

Us the following procedure for calibrating the relay if
the relay has been taken apart for repairs or the
adjustments disturbed. This procedure should not be
used until it is apparent that the relay is not in proper
working order. (See “Acceptance Check”).

8.1. MAIN UNITS

For all electrical checks refer to test diagram figure 5.
For tapped CM, put tap screw in one amp tap setting.

1.

Balance Setting

a)

Mechanical balance - adjust spiral spring

until moving contact is located substantially
in the center of the scale plate.

b)

Electrical Balance

1.

Apply two amperes on front and rear

electromagnets and adjust resistor at
rear of specific unit being tested such
that the moving contact is in balance,
i.e., moving contact is aligned per part
“a” above.

2.

Apply twenty amperes on front and rear

electromagnets for approximately two
seconds and note that the moving con-
tact does not deviate from the balanced
condition more than approximately 1/4
inch.

For CM relays with adjustable magnetic plugs, only
the right-hand plug may be adjusted. At the factory,
the right-hand plug is adjusted to help obtain a bal-
anced condition of the contact at 20 amperes. The
moving contact is again checked at 2 amperes. Little
adjustment, if any, is expected to be necessary in the
field.

2.

Minimum Trip Setting

The front electromagnet energized alone should

produce a disc rotation to the left while the rear
electromagnet energized alone should produce a
disc rotation to the right.

a)

Apply one ampere to front electromagnet

and adjust left stationary contact until it just
makes with the moving contact. This setting
should correspond with the marking on scale
plate.

b)

Apply one ampere to rear electromagnet and

adjust right stationary contact until it just
makes with the moving contact. This setting
should correspond with marking on scale
plate.

3.

Operating Curve

Apply six amperes to front electromagnet and

vary current flowing through rear electromagnet.

a)

The moving contact should make with the

Summary of Contents for CM

Page 1: ...has a pair of electromagnets operat ing on a single disc The disc is damped by a perma nent magnet Each disc carries its own set of contacts with the two sets being connected in paral lel in order that either disc may close the trip circuit The electromagnet pair are mounted face to face on opposite sides of the disc and so connected that the electrical torque of one electromagnet opposes that of ...

Page 2: ...41 181 2K 2 Figure 1a Non Tapped Type CM Relay without case Front View Figure 1b Non Tapped Type CM Relay without case Rear Vies ...

Page 3: ...3 41 181 2K Figure 2a Type CM Tapped Relay without case Front View Figure 2b Type CM Tapped Relay without case Rear View ...

Page 4: ...ont of the switch which allows the operation indicator target to drop 3 0 CHARACTERISTICS The non tapped type CM relay has a minimum pickup current of one ampere and a continuous ther mal rating of seven amperes The tapped CM relay has a minimum pickup of 1 2 or 3 amperes depend ing on the tap setting and a continuous of 7 amperes The minimum pickup current is defined as the pickup current of each...

Page 5: ...y means of the four mounting holes on the flange for the semi flush type FT case Either the stud or the mounting screws may be utilized for grounding the relay Exter nal toothed washers are provided for use in the loca tions shown on the outline and drilling plan to facilitate making a good electrical connection between the relay case its mounting screws or studs and the relay panel Ground wires a...

Page 6: ...y one ampere through the front and rear electromagnets simultaneously The moving contact should remain substantially midway between the stationary contacts A similar check should be made utilizing six amperes 4 Time Curve Contact travel is from balanced position to either the right or left stationary contacts Electromagnets are to be energized alone zero restraint Apply ten amperes and note that c...

Page 7: ...has been taken apart for repairs or the adjustments disturbed This procedure should not be used until it is apparent that the relay is not in proper working order See Acceptance Check 8 1 MAIN UNITS For all electrical checks refer to test diagram figure 5 For tapped CM put tap screw in one amp tap setting 1 Balance Setting a Mechanical balance adjust spiral spring until moving contact is located s...

Page 8: ...his value of current should not be greater than the particular ICS tap setting being used The operation indicator target should drop freely 8 3 AC INDICATING CONTACTOR SWITCH ACS Close the main relay contacts and pass sufficient ac current through the trip circuit to close the contacts of the ACS This value of current should not be greater than the particular ACS rated operating current being used...

Page 9: ...9 41 181 2K Figure 7 Internal Schematic of the Non Tapped Type CM Relay in the Type FT 31 Case Figure 8 Internal Schematic of the Tapped Type CM Relay in the Type FT 31 Case 187A232 762A812 ...

Page 10: ...41 181 2K 10 Figure 9 Element Assembly for CM Relay Front View ...

Page 11: ...11 41 181 2K Figure 10 External Schematic Diagram of the Type CM Relay in the Type FT 31 Case Sub 4 188A144 Figure 10 External Schematic Diagram of the Type CM Relay in the Type FT 31 Case ...

Page 12: ...ion Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd 41 181 2K Figure 11 External Schematic Diagram of the Type CM Relay in the Type FT 31 Case 57S902 ...

Reviews: