Complete parameter-definition
In order to parameter-define the controller completely, the steps
provided below must be processed consecutively.
Key
Display
Parameter
Parameter values
underlined or FS = Factory Setting
change
Main operator level
for at
least 6 s
defines the alarm setpoint value for the alarm con-
figured under
. Depending on the type of alarm
defined for the parameter
, this can be either an
absolute alarm value or a deviation alarm value (see
also Section on “Alarms”).
•
absolute alarm value in the range
...
, if
= 0, 1, 4, 5
•
relative alarm value in the
range
...
, if
= 2, 3, 6,
7, 8, 9, 10, 11
•
time value in the range 0... 3600 min,
if
= 12 or 13
FS 200
°
C
,
defines the setpoint ramp rate to allow the process to
reach the new setpoint via a linear ramp after setpoint
change.
•
0...200
°
C/min (360
°
F/min), if
=
0 to 9
•
0...3600 digit/min, if
= 10
,
defines the offset value for manual reset (= operating
point), if
= 0, i.e. the output signal of the controller
is shifted by
.
Notice
This parameter is only required when the controller
does not use any integral component (integral action
time
).
0.0...100 %
,
defines the offset shift for the process variable in the
display (measured value correction).
Example
The display shows 1
°
C less than the actual
temperature. This can be corrected with an input of
+1
°
C.
−111...0...+111
°
C
,
defines the proportional range of output 1 (heating)
Notice
Changing this parameter has decisive effects on the
control action.
0...10...200
°
C (0 for ON/OFF control)
,
8
Parameter definition