Key
Display
Parameter
Parameter values
underlined or FS = Factory Setting
change
defines the number of decimal points
0
No decimal places
1
One decimal place
2
Two decimal places (only when
= 10)
3
Three decimal places (only when
= 10)
,
defines the control action for the output
0
direct (cool)
1
inverse (heat)
,
defines the reaction in case of sensor break
Output
Alarm
0
Off
Off
1
Off
On
2
On
Off
3
On
On
,
defines the hysteresis for On/Off control
0...0.5...20 % of the measuring range
,
defines the lower-range value (low limit)
depends on the sensor
FS depends on the sensor
,
defines the upper-range value (high limit)
depends on the sensor
FS depends on the sensor
,
or
PV
return to the main operator level
or to 2. menu level
for at
least 6 s
lower calibration point for recalibration
depends on the sensor
FS depends on sensor
,
upper calibration point for recalibration
depends on sensor
FS depends on sensor
,
return to the main operator level
Parameter definition
11