CBXi IP Controller |
Installation
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
35
MAN
01
41
re
v 2
3
Note
: If the default IP address is used on a network, it can cause an
IP Address
conflict if the network’s
subnet
mask is
10.0.0.0/8
(see
It may be possible to reach the CBXi over the network but BACnet messaging may fail.
In this case you may need to use a directly-connected laptop, or a different network to configure
the
CBXi
. Alternatively you could change the
CBXi
’s
subnet mask
to
10.ss.ss.ss/24
, (where
ss
is the
serial number) to reduce the size of the
subnet
that could give rise to conflicts. For example, a
CBXi
with serial number
901001A
should have a subnet mask of
10.90.10.01/24
.
Accessing the CBXi’s Web
UI
Point a web browser at the
CBXi
device’s
IP
address, and log in to the Web UI.
Note
: By default, all
CBXi
devices leaving the factory are configured with the following login:
username:
admin
password:
cylonctl
It is recommended that you change these credentials by clicking on the User icon in the top-right of the
Web UI page and selecting
Change Password
.