CBXi IP Controller |
Installation
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
60
MAN
01
41
re
v 2
3
Add
strategy
blocks
and
points
to create the required
strategy
–
see
MAN0133 CXpro
ᴴᴰ
User Guide
for
more detail.
Note:
In
CBXi-8R8(-H)
controllers there are:
•
A total of 1500 strategy blocks, numbered 1 - 1500
•
A maximum of 640 exposed BACnet points
•
A minimum of 16 and a maximum of 64 hardware points:
◦
The first 16 are numbered 1 - 16, representing the internal I/O in the CBXi
◦
The 16 points in an attached
FLX
with
MS/TP
address set to “
1
” are numbered
101
…
116
◦
The 16 points in an attached
FLX
with
MS/TP
address set to “
2
” are numbered
201
…
216
◦
The 16 points in an attached
FLX
with
MS/TP
address set to “
3
” are numbered
301
…
316