5. Electrical connections
5.1. Connections to the power circuit
5.1.1. Shapes of the terminals
Note
The drawings are provided to show the type of terminal in graphic form. The exact shape of the terminals is given in the “Overall
dimensions” chapter.
5.1.2. Examples of positioning the connection busbars according to the types of terminals
The connection busbars enable the connection between the terminals of the circuit-breakers and the busbars of the switchgear. Their
sizing must be carefully studied by the switchgear designer. Some examples of possible constructions in relation to the shape and
size of the circuit-breaker terminals are given in this paragraph. The various types of terminals are of constant dimensions for each
size of circuit-breaker: it is normally advisable to exploit the whole contact surface of the terminal, so the width of the connection
busbars should be the same as that of the terminal. Different connection capacities can be obtained by adjusting the thickness and
number of busbars in parallel. In some cases, reductions in the width of the connection in relation to that of the terminal are allowable
as shown in the following examples.
Vertical terminals
Horizontal terminals
Circuit-breaker
Iu [A]
Continuous current-
carrying capacity
Busbar cross-
section
Continuous current-
carrying capacity
Busbar cross-
section
[A] (50÷60Hz)
[mm
2
]
[A](50÷60Hz)
[mm
2
]
35°C
45°C
55°C
35°C
45°C
55°C
E2N/VF 12
1200
1200
1200
1200
1x(60x10)
1200
1200
1200
1x(60x10)
E2N/VF 16
1600
1600
1600
1600
2x(60x10)
1600
1600
1530
2x(60x10)
E3H/VF 20
2000
2000
2000
2000
2x(100x10)
2000
2000
2000
2x(100x10)
E3H/VF 25
2500
2500
2500
2500
2x(100x10)
2500
2450
2400
2x(100x10)
Fig. 16
Positioning the first anchoring baffle of the busbars according to the short-circuit current
Fig. 17
Anchoring to the switchgear
VERTICAL
HORIZONTAL
P
E2
E3
HORIZONTAL
250
150
VERTICAL
250
150
HR
VR
HR
VR
Fig. 14
Fixed part for withdrawable circuit-breaker
Fig. 15
Fixed circuit-breaker
Horizontal rear terminals
Vertical rear terminals
Horizontal rear terminals
Vertical rear terminals