6
OI/ADS430/EZCLN–EN Rev. B
| Aztec ADS430 EZCLEAN | Compressed air supply unit
3 Installation
3.1 Wall-mounting
This procedure is for wall-mounting using the 4 x plastic
wall-mounting lugs and M6 screws / washers (supplied). The
lugs can be attached to the unit in the vertical or horizontal
plane. When choosing the mounting location, leave sufficient
space in front of the unit to open the door fully (280 mm
[11.0 in.]).
Referring to Fig. 3.1:
1.
Fit the 4 x mounting lugs
A
to the compressor unit
B
in
the required plane and secure using the M6 screws /
washers
C
.
2.
Mark appropriate mounting lug screw hole locations on the
wall and drill suitably-sized holes to accommodate the
mounting location disks
D
and fixings
E
(not supplied).
3.
Mount the compressor unit to the wall.
WARNING – Bodily injury
Unit weight 10.3 kg (22.6 lbs.). Mount in accordance
with relevant safety requirements using suitable
equipment and personnel.
IMPORTANT (NOTE)
Ensure the keyhole slots in location disks
D
are
aligned correctly.
Dimensions in mm (in.)
*Add 280 (11.0) when door open
Fig. 3.1 Wall-mounting
381
(15.0)
262
(10.3)
420
(16.5)
440
(17.3)
196
(7.7)
330
(13.0)
395
(15.5)
205