INSTALLATION
WIRING TYPE AV2 POSITIONER
3 - 11
for detailed information about position trans-
mitters.
NOTE:
Route the wiring inside the positioner so it does not
become entangled with moving parts. A cable clamp (Figs.
and
) is provided inside the positioner so entanglement can
be avoided.
4. Grounding positioners should be done in accordance with
local electrical codes (in U.S, National Electrical Code, ANSI/
NFPA 70. In Canada, Canadian Electrical Code, CSA c22.1). A
grounding screw is provided inside the enclosure for grounding,
denoted by .
NOTES:
1.
The grounding screw located inside the enclosure is a safety
ground and should not be used to ground the shielded pair.
2.
The positioner must be grounded to avoid ground loop
conditions.
Figure 3-10. Direct Acting, Top Loaded,
Single Acting Tubing Example
HANDJACK
T00890A
O1
OUTPUT GAGE (O1 PORT)
SIGNAL GAGE
ALTERNATE PIPING FOR
DIAPHRAGM ACTUATOR
WITH HANDJACK
MOTION WITH
INCREASING SIGNAL
NOTES:
1. BLACK CAM ROTATES COUNTERCLOCKWISE
WHEN VIEWED FROM THE FRONT.
2. O2 PORT PLUGGED.
3. STEM MOVES UP WITH SIGNAL OR SUPPLY
AIR FAILURE.
G2
G1