47
O U T L I N E D R AW I N G S , O R D ER I N G I N FO R M AT I O N
—
Ordering information
ADVAC® 38 breaker smart-style numbering
Ordering of the ADVAC 38
The ADVAC 38 kV breaker product line has a
structured, smart-style number ordering system.
The complete style number is built up of 16
customer-selected digits. Each digit identifies
features or functions that can be incorporated into
the breaker application. The first five digits of the
style number define the basic breaker. The next
three digits define electrical control options. The
last seven digits are used to define various options.
How to create an ADVAC 38, 16-digit smart-style
ordering number:
Step 1: Specify “A” for ADVAC circuit breaker for
digit 1.
Step 2: Select the breaker type, A = drawout, B = roll
on the floor, F = fixed or stationary for digit 2.
Step 3: Specify “4” for EL type, also know as model
4 ADVAC circuit breaker for digit 3.
Step 4: Select the system ratings according to the
table below for digits 4 and 5.
See following page for continuation of ordering
steps.
ADVAC® 38 style number digits 4–5
Digits 4–5
kV class
Max wave
voltage (kV)
Continuous
current (A)
Short circuit
current (A)
BtB C2 capacitive
switching (A)
W1
38
1200
16
W2
2000
16
W3
3000 FAC
16
X1
1200
25
X2
2000
25
X3
3000 FAC
25
Y1
1200
31.5
Y2
2000
31.5
Y3
3000 FAC
31.5
Z1
1200
40
1000
Z2
2000
40
1000
Z3
40.5
3000 FAC
40
1000
A
B
4
Z
3
7
7
7
0
0
0
N
0
0
0
0
ADVAC prefix
Cell type
Cell interface
kV class, current,
capacitive switching
Charge motor voltage
Close coil voltage
Open coil voltage
Second open coil
Undervoltage device
Engineering special
Labeling
Pushbutton cover options
Truck option
Non-standard colors
Ground contact
Sample style
number