268 Parameters
Defines the minimum torque limit for the drive (in percent of
nominal motor torque) when
• the source selected by parameter
is 1, and
•
Note:
Do not set this parameter to 0% in an attempt to prevent
reverse rotation. In an open-loop application, that is likely to
prevent the motor from stopping altogether. To prevent
reverse rotation, use the speed/frequency limits in this
parameter group, or parameters
See diagram at
-300.0%
-1600.0 … 0.0%
Minimum torque limit 2.
See par.
Defines the maximum torque limit for the drive (in percent of
nominal motor torque) when
• the source selected by parameter
is 1, and
•
See diagram at
300.0%
0.0 … 1600.0%
Maximum torque limit 2.
See par.
Selects a source that switches between two different
maximum torque limits.
0 = Maximum torque limit 1 defined by
is active
1 = Maximum torque limit selected by
is active
.
Maximum torque 1
0.
0
Maximum torque 2
source
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
). -
Defines the maximum shaft power in motoring mode, ie. when
power is being transferred from the motor to the machinery.
The value is given in percent of nominal motor power.
300.00%
0.00 … 600.00%
Maximum shaft power in motoring mode.
1 = 1%
Defines the maximum shaft power in generating mode, ie.
when power is being transferred from the machinery to the
motor. The value is given in percent of nominal motor power.
Note:
Do not set this parameter to 0% in an attempt to prevent
reverse rotation. In an open-loop application, that is likely to
prevent the motor from stopping altogether. To prevent
reverse rotation, use the speed/frequency limits in this
parameter group, or parameters
-300.00%
-600.00 … 0.00%
Maximum shaft power in generating mode.
1 = 1%
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...