222 Parameters
Defines the shape of the acceleration ramp at the beginning of
the acceleration.
0.000 s: Linear ramp. Suitable for steady acceleration or
deceleration and for slow ramps.
0.001…1000.000 s: S-curve ramp. S-curve ramps are ideal
for lifting applications. The S-curve consists of symmetrical
curves at both ends of the ramp and a linear part in between.
Note:
For safety reasons, shape times are not applied to
emergency stop ramps.
Acceleration:
Deceleration:
0.000 s
0.000 …1800.000 s Ramp shape at start of acceleration.
10 = 1 s
Defines the shape of the acceleration ramp at the end of the
acceleration. See parameter
0.000 s
0.000 …1800.000 s Ramp shape at end of acceleration.
10 = 1 s
Defines the shape of the deceleration ramp at the beginning
of the deceleration. See parameter
.
0.000 s
0.000 …1800.000 s Ramp shape at start of deceleration.
10 = 1 s
No.
Name/Value
Description
Def
/
FbEq16
S-curve ramp:
> 0 s
Linear ramp:
= 0 s
Linear ramp:
S-curve ramp:
> 0 s
Speed
Time
Shape time
S-curve ramp:
> 0 s
Linear ramp:
= 0 s
S-curve ramp:
Speed
Time
Linear ramp:
= 0 s