272 Parameters
Defines a feedback delay for the motor fan.
The delay timer starts when bit 1 of
switches on. If
no feedback is received from the fan until the delay
elapses, the action selected by
is taken.
Note:
This delay is only applied at start. If the feedback
signal is lost during run, the action selected by
taken immediately.
0 s; 5s
(
b6)
0…42949673 s
Motor fan start delay.
1 = 1 s
Status of the motor fan control logic.
Bit 1 is the control output for the fan, to be selected as the
source of, for example, a digital or relay output.
The other bits indicate the statuses of the selected control
and feedback sources, and the fault status.
This parameter is read-only.
-
0000b…1111b
Status of motor fan control logic.
1 = 1
Selects the action taken when missing fan feedback is
detected by the motor fan control logic.
No action
No action taken.
0
Warning
The drive generates a warning (
1
Fault
Drive trips on
.
2
36
Peak value and amplitude logger settings.
See also section
Selects the signal to be monitored by the peak value
logger.
The signal is filtered using the filtering time specified by
parameter
.
The peak value is stored, along with other pre-selected
signals at the time, into parameters
…
.
The peak value logger can be reset using parameter
. The date and time of the last reset are
stored into parameters
and
respectively.
Zero
None (peak value logger disabled).
0
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
Start command
Status of fan control source selected by
.
0 = Stop requested
1 = Start requested
1
Delayed start
command
Fan control bit (delays observed). Select this bit as the source
of the output controlling the fan.
0 = Stopped
1 = Started
2
DOL feedback
Status of fan feedback (source selected by
0 = Stopped
1 = Running
3
DOL fault (-1)
Fault status.
0 = Fault (fan feedback missing). The action taken is selected
by
.
1 = No fault
4…15
Reserved
Summary of Contents for ACS880 PCP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...