WARNING!
Use the required personal protective equipment. Wear protective gloves and long
sleeves. Some parts have sharp edges.
Keep the module in its package until you install it. After unpacking, protect the
module from dust, debris and moisture.
Lift/lower a heavy module with a lifting device. Use the designated lifting points.
See the dimension drawings. There is a lifting device available from ABB (order
code 3AXD50000047447).
Make sure that the drive cabinet is attached to the floor to prevent it from toppling
over. The cabinet has a high center of gravity. When you pull out heavy components
or power modules, there is a risk of overturning.
1.
Stop the motors connected to the drive.
2.
Repeat the steps described in section
Electrical safety precautions (page 36)
.
3.
Open the cubicle door.
4.
Close the inlet and outlet valve.
5.
Lead the drain hoses into a suitable container. If necessary, extend the hoses. Open
the inlet and outlet drain valves. This will drain all modules in the cubicle.
6.
After the cubicle has drained, disconnect the piping from the module.
7.
2×D8T module: If lower module needs to be replaced, remove the cooling fan (see the
fan replacement instructions).
8.
Remove any shrouding above the module.
9.
Remove the DC fuses above the module. See section
10. Disconnect the plug connector and fiber optic connectors in front of the module.
11. Remove the L-shaped busbars (3 pcs above the module).
12. Remove the module fastening screws (4 pcs).
13. Install the module lifting device to the cabinet. See
Converter module lifting device for
drive cabinets hardware manual
(3AXD50000210268 [English]).
14. Attach one lifting hook to the front lifting eye of the module and pull the module out 10
centimeters. Keep the lifting chain tight.
15. Attach the second lifting hook to the rear lifting eye, and pull the module completely out
of the cabinet. Keep the weight constantly on the lifting device.
Maintenance 71
Summary of Contents for ACS880-307LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 307LC diode supply units Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 34: ...34 ...
Page 41: ...10 9 7 6 8 Electrical installation 41 11 ...
Page 73: ...11 12 12 6 10 Maintenance 73 ...
Page 78: ...78 ...
Page 88: ...88 ...
Page 96: ... 400 mm wide input cubicle 96 Technical data ...
Page 97: ... 600 mm wide incoming cubicle or input cubicle Technical data 97 ...