Heavy-duty use
Light overload
use
No overload use
Supply unit
type
ACS880-
307LC-…
P
Hd
I
Hd
P
Ld
I
Ld
P
N
I
max_2
S
N
I
max_1
I
2
I
1
kW
(DC)
A (DC)
kW
(DC)
A (DC)
kW
(DC)
A (AC)
kVA
A (DC)
A (DC)
A (AC)
1255
1346
1610
1728
1677
2205
1757
2700
1800
1470
1470A-7
+A004+A018
1708
1833
2192
2352
2283
3000
2390
3675
2450
2000
2000A-7
+A004+A018
2509
2693
3220
3456
3355
4410
3514
5400
3600
2940
2940A-7
+A004+A018
3415
3665
4383
4704
4566
6000
4780
7350
4900
4000
4000A-7
+A004+A018
5123
5498
6575
7056
6849
9000
7171
11025
7350
6000
6000A-7
+A004+A018
Definitions
Nominal ratings
U
N
Nominal input voltage. For
U
1
, see
. For
U
2
, see DC connection data.
I
1
Continuous rms input (AC) current. No overload capability at the coolant
temperature of 40 °C (104 °F) and air temperature of 45 °C (113 °F).
I
2
Continuous rms output (DC) current. No overload capability at the coolant
temperature of 40 °C (104 °F) and air temperature of 45 °C (113 °F).
I
max_1
Maximum output (DC) current. Available for 10 s at start, otherwise as long as
allowed by module temperature.
S
N
Nominal apparent (AC) power
I
max_2
Maximum input (AC) current
P
N
Nominal output (DC) power
Light-overload use (50% overload capability) ratings
I
Ld
Continuous current. 50% overload is allowed for one minute every 5 minutes.
P
Ld
Output power in light-overload use
Heavy-duty use (50% overload capability) ratings
I
Hd
Continuous current. 50% overload is allowed for one minute every 5 minutes.
P
Hd
Output power in heavy-duty use
Derating
■
Surrounding air temperature derating
In the temperature range +45…55 °C (+113…131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be calculated
by multiplying the current given in the rating table by the derating factor
(k)
:
90 Technical data
Summary of Contents for ACS880-307LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 307LC diode supply units Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 34: ...34 ...
Page 41: ...10 9 7 6 8 Electrical installation 41 11 ...
Page 73: ...11 12 12 6 10 Maintenance 73 ...
Page 78: ...78 ...
Page 88: ...88 ...
Page 96: ... 400 mm wide input cubicle 96 Technical data ...
Page 97: ... 600 mm wide incoming cubicle or input cubicle Technical data 97 ...