Typical power cable sizes
This table gives aluminum and copper cable types. The cable sizing is based on max.
9 cables laid on the cable trays side by side, three ladder type trays one on top of the
other, ambient temperature 30 °C (EN 60204-1 and IEC 60364-5-52). A correction factor
K = 0.70 is used.
Copper cable
Aluminum cable
Frame
size
XLPE insulation
PVC insulation
XLPE insulation
PVC insulation
Conductor temperature T=90 °C
Conductor tem-
perature T=70 °C
Conductor tem-
perature T=90 °C
Conductor tem-
perature T=70 °C
Size mm
2
Size mm
2
Size mm
2
Size mm
2
U
N
= 690 V
or 3×(3×150+70)
4×(3×95+50)
4×(3×150+70)
4×(3×150+41 Cu)
4×(3×240+72 Cu)
1×D8D
or
2×3×(3×150+70)
2×4×(3×95+50)
2×4×(3×150+70)
2×4×(3×150+41
Cu)
2×4×(3×240+72
Cu)
2×D8D
Connecting the power cables and busbars
■
Connection diagrams
The following connection diagrams show how connection and grounding of the supply
modules and their switchgear can be arranged.
The switchgear and modules are typically grounded to the frame of the cabinet via
the fixing screws. If good enough electrical contact for grounding is not possible via
the fastening screws and cabinet frame, the cabinet installer must use a separate
grounding.
The diagrams show also a separate charging circuit and supply transformer. For more
information on them, see section
Selecting the supply transformer
The connection diagrams in this section are simplified. They do not contain all details,
such as terminal markings, and are not suitable for the installation work as such. The
designer of the cabinet must:
•
prepare the final circuit diagrams
•
provide the final circuit diagrams to the installer(s).
The electricians that do the connections must use the final circuit diagrams.
Electrical installation 61
11
Summary of Contents for ACS880-304LC Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 304LC A019 diode supply modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 30: ...30 ...
Page 34: ...34 ...
Page 46: ... Stage 1 Installation of common parts 46 Cabinet construction ...
Page 47: ... Stage 2 Module installation parts Cabinet construction 47 10 ...
Page 48: ... Stage 3 Liquid cooling system components 48 Cabinet construction ...
Page 49: ... Stage 4 AC and DC busbar installation Cabinet construction 49 10 ...
Page 50: ... Stage 5 AC and DC connection 50 Cabinet construction ...
Page 51: ... Stage 6 Cabinet fan and heat exchanger Cabinet construction 51 10 ...
Page 52: ... Stage 7 Shroud installation parts 52 Cabinet construction ...
Page 53: ... Stage 8 Door covers and explosion exhaust kit Cabinet construction 53 10 ...
Page 54: ...54 ...
Page 74: ...74 ...
Page 87: ...5 Maintenance 87 ...
Page 88: ...6 7 8 9 9 88 Maintenance ...
Page 92: ...92 ...
Page 108: ...108 ...
Page 118: ...118 ...
Page 140: ...Liquid cooled D8D module Dimensions in mm 1 mm 0 0394 in 140 Dimension drawings ...
Page 142: ...ZCU 14 control unit 142 Dimension drawings ...
Page 143: ...Support plate for ZCU 14 UDZKROH 0 GRZQ UDZKROH 0 GRZQ Dimension drawings 143 ...
Page 144: ...CIO 01 module 144 Dimension drawings ...
Page 152: ...152 ...