Cabinet temperature supervision
In liquid-cooled drive systems, the cabinet can be totally sealed from the ambient air.
The air inside the cabinet must be able to circulate freely. You can install a fan inside
the cabinet to push air through a heat exchanger.
You can use thermal switches [F6.11, F6.12] to supervise the temperature inside the
cabinet. Install the thermal switches on the hottest element of the cabinet. In this
example, the thermal switches are on the DC busbar above the supply module (two
thermal switches for 1×D8D and 2×D8D modules on the DC+ and DC- busbars). ABB
recommends to use thermal switches with 100 °C temperature limit.
Wire the switch to a digital input (DI) of the supply control unit (1 = OK,
0 = overtemperature). In case of overtemperature, the switch opens and the control
program generates first a warning, and then, if the overtemperature indication remains
over a predefined delay, trips the supply unit on a fault. You can adjust the delay time
by parameters. For the example wirings, see the example circuit diagrams.
Note: If you install the switches on the busbars, make sure there is proper insulation
between the busbars and thermal switches.
Cabinet construction 39
10
Summary of Contents for ACS880-304LC Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 304LC A019 diode supply modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 30: ...30 ...
Page 34: ...34 ...
Page 46: ... Stage 1 Installation of common parts 46 Cabinet construction ...
Page 47: ... Stage 2 Module installation parts Cabinet construction 47 10 ...
Page 48: ... Stage 3 Liquid cooling system components 48 Cabinet construction ...
Page 49: ... Stage 4 AC and DC busbar installation Cabinet construction 49 10 ...
Page 50: ... Stage 5 AC and DC connection 50 Cabinet construction ...
Page 51: ... Stage 6 Cabinet fan and heat exchanger Cabinet construction 51 10 ...
Page 52: ... Stage 7 Shroud installation parts 52 Cabinet construction ...
Page 53: ... Stage 8 Door covers and explosion exhaust kit Cabinet construction 53 10 ...
Page 54: ...54 ...
Page 74: ...74 ...
Page 87: ...5 Maintenance 87 ...
Page 88: ...6 7 8 9 9 88 Maintenance ...
Page 92: ...92 ...
Page 108: ...108 ...
Page 118: ...118 ...
Page 140: ...Liquid cooled D8D module Dimensions in mm 1 mm 0 0394 in 140 Dimension drawings ...
Page 142: ...ZCU 14 control unit 142 Dimension drawings ...
Page 143: ...Support plate for ZCU 14 UDZKROH 0 GRZQ UDZKROH 0 GRZQ Dimension drawings 143 ...
Page 144: ...CIO 01 module 144 Dimension drawings ...
Page 152: ...152 ...