Dimensions, weights and free space requirements
■
Dimensions and weights
See the dimension drawing.
■
Free space requirements
The values are as required by cooling, maintenance and/or operation of the pressure relief
(if present).
Above
Sides
Front
in
mm
in
mm
in
mm
9.85
250
0
0
5.90
1500
Losses, cooling data and noise
Noise
1)
Coolant
quantity
(total)
Heat dissipation
Coolant flow
ACS880-207LC-…
dB(A)
l
into air (kW)
into coolant
(kW)
US gal/min
l/min
U
N
= 690 V
58
8.1
0.2
8.9
13.7
52
0360A-7
58
8.1
0.3
9.8
13.7
52
0400A-7
58
8.1
0.3
11.1
13.7
52
0450A-7
58
8.1
0.3
12.0
13.7
52
0480A-7
58
8.1
0.4
14.1
13.7
52
0560A-7
58
8.1
0.4
15.7
13.7
52
0620A-7
58
8.1
0.5
18.4
13.7
52
0700A-7
58
8.1
0.5
20.9
13.7
52
0770A-7
59
11.3
0.5
21.3
23.2
88
0930A-7
59
11.3
0.6
25.3
23.2
88
1090A-7
59
11.8
0.7
28.6
23.2
88
1180A-7
59
11.8
0.8
31.0
23.2
88
1360A-7
59
11.8
0.9
35.1
23.2
88
1500A-7
61
18.7
1.0
39.3
38.0
144
1800A-7
61
18.7
1.2
45.6
38.0
144
2020A-7
61
18.7
1.3
51.7
38.0
144
2220A-7
61
23.6
1.5
58.6
42.3
160
2670A-7
61
23.6
1.7
66.2
42.3
160
2930A-7
62
30.0
1.9
73.8
57.1
216
3320A-7
63
34.1
2.1
83.8
69.7
264
3840A-7
63
37.4
2.6
100.6
74.0
280
4360A-7
64
43.3
2.9
113.9
78.2
296
5240A-7
64
46.6
3.3
130.3
82.4
312
5810A-7
1) Measured in a hemi-anechoic room in accordance with ISO 9614-2 standard.
Technical data 95
Summary of Contents for ACS880-207LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 207LC IGBT supply units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 52: ...52 ...
Page 62: ...62 ...
Page 74: ...4 74 Maintenance ...
Page 79: ...4 5 6 Maintenance 79 ...
Page 96: ...Internal cooling circuit data See chapter Internal cooling circuit 96 Technical data ...
Page 98: ...98 Technical data ...
Page 99: ... 600 mm wide incoming cubicle or input cubicle Technical data 99 ...
Page 100: ... 1000 mm wide input cubicle 100 Technical data ...
Page 108: ...108 ...
Page 118: ...118 ...