Action
Powering up the main circuit of the drive
Close the main switch-disconnector [Q1.1] or main breaker [Q1].
Note:
Do not use excessive force. The main switch-disconnector (or main breaker) can only be closed
when
• the main input terminals [L1, L2, L3] are powered, and
• auxiliary voltage is switched on [Q21], and
Turn the operating switch (S21) to the ON (1) position to activate the run enable signal. Depending on
control source settings, this may also close the main contactor (if present). If a main contactor is present
and does not close, refer to the circuit diagrams delivered by the drive as well as the appropriate firmware
manuals.
On-load checks
Start the motor to perform the ID run.
Check that the cooling fans rotate freely in the right direction, and the air flows upwards.
Check that the motor starts. stops and follows the speed reference in the correct direction when controlled
with the control panel.
Check that the motor starts. stops and follows the speed reference in the correct direction when controlled
through the customer-specific I/O or fieldbus.
Drives in which the Safe torque off control circuit is in use: Test and validate the operation of the Safe
torque off function. See section
Start-up including acceptance test (page 209)
Drives with an emergency stop circuit (oQ951, +Q952, +Q963, +Q964, +Q978, +Q979): Test
and validate the operation of the emergency-stop circuit. See the delivery specific circuit diagrams and
wiring, start-up and operating instructions of the option.
Switching off the drive
1.
Stop the motor.
2.
Turn the Run enable switch (S21) to the off (0) position to deactivate the Run enable
signal and to switch the main contactor/breaker off.
Start-up 123
12
Summary of Contents for ACS880-07LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 07LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...16 Resistor braking Further information 12 Table of contents ...
Page 22: ...22 ...
Page 63: ...Mechanical installation 63 10 ...
Page 64: ...64 ...
Page 91: ...a b c 4 a 8 b 16 18 PE PE 10 13 12 Electrical installation 91 11 ...
Page 100: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 100 Electrical installation ...
Page 104: ...104 ...
Page 118: ...118 ...
Page 124: ...124 ...
Page 138: ...8 9 138 Maintenance ...
Page 139: ...11 12 12 6 10 Maintenance 139 ...
Page 150: ...150 ...
Page 160: ...160 ...
Page 183: ...Technical data 183 ...
Page 184: ...184 Technical data ...
Page 189: ... Dimension drawing examples ACS880 07LC 0850A 7 Dimensions 189 ...
Page 190: ...ACS880 07LC 1660A 7 6 pulse 190 Dimensions ...
Page 191: ...ACS880 07LC 1660A 7 A004 12 pulse Dimensions 191 ...
Page 192: ...ACS880 07LC 3260A 7 192 Dimensions ...
Page 195: ... 600 mm with main breaker double busbar bottom cable entry Dimensions 195 ...
Page 197: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 197 ...
Page 198: ...Inverter module cubicle with three R8i modules bottom cable exit 198 Dimensions ...
Page 199: ...Brake chopper cubicle Dimensions 199 ...
Page 200: ...200 ...
Page 216: ... Declaration of conformity 216 The Safe torque off function ...
Page 217: ...The Safe torque off function 217 ...
Page 218: ...218 ...
Page 220: ...220 ...