Thermal protection with PTC relays (oL505, +2L505, +L513,
+2L513, +L536, +L537)
PTC thermistor relay options are used for overtemperature supervision of motors equipped
with PTC sensors. When the motor temperature rises to the thermistor wake-up level, the
resistance of the sensor increases sharply. The relay detects the change and indicates
motor overtemperature through its contacts.
+L505, +2L505, +L513, +2L513
L505 provides a thermistor relay and a terminal block. The terminal block has
connections for the measuring circuit (one to three PTC sensors in series), an output
indication of the relay, and an optional external reset button. The relay can be reset either
locally or externally, or the reset circuit can be jumpered for automatic reset.
By default, the thermistor relay is wired internally to digital input DI6 of the drive control unit.
The loss of the input is set to trigger an external fault.
The output indication on the terminal block can be wired by the customer, for example, to
an external monitoring circuit. See the circuit diagrams delivered with the drive.
L513 is an ATEX-certified thermal protection function that has the same external
connectivity as +L505. In addition, +L513 comes with +Q971 (ATEX-certified safe
disconnection function) as standard and is wired at the factory to activate the Safe torque
off function of the drive in an overtemperature situation. A manual reset for the protection
function is required by Ex/ATEX regulations. For more information, see
ATEX-certified motor
thermal protection functions for cabinet-built ACS880 drives (oL513+Q971 and
+L514+Q971) user's manual
(3AXD50000014979 [English]).
O2L505 and +2L513 duplicate oL505 and +L513 respectively, containing
the relays and connections for two separate measurement circuits.
+L536, +L537
An alternative to a thermistor relay option is the FPTC-01 (L536) or FPTC-02 (+L537,
also reQ971) thermistor protection module. The module mounts onto the inverter
control unit, and has reinforced insulation to keep the control unit PELV-compatible. The
connectivity of the FPTC-01 and the FPTC-02 is the same; FPTC-02 is Type Examined as
a protective device within the scope of the European ATEX Product Directive.
For protection purposes, the FPTC has a "fault" input for the PTC sensor. An overtemperature
situation executes the SIL/PL-capable SMT (Safe motor temperature) safety function by
activating the Safe torque off function of the drive.
The FPTC also has a "warning" input for the sensor. When the module detects
overtemperature through this input, it sends a warning indication to the drive.
For more information and wiring examples, see the module manuals and the circuit diagrams
delivered with the drive.
See also
•
firmware manual for parameter settings
•
ATEX-certified motor thermal protection functions for cabinet-built ACS880 drives
(oL513+Q971 and +L514+Q971) user's manual
(3AXD50000014979 [English])
•
FPTC-01 thermistor protection module (L536) for ACS880 drives user's manual
(3AXD50000027750 [English])
Operation principle and hardware description 41
Summary of Contents for ACS880-07LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 07LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...16 Resistor braking Further information 12 Table of contents ...
Page 22: ...22 ...
Page 63: ...Mechanical installation 63 10 ...
Page 64: ...64 ...
Page 91: ...a b c 4 a 8 b 16 18 PE PE 10 13 12 Electrical installation 91 11 ...
Page 100: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 100 Electrical installation ...
Page 104: ...104 ...
Page 118: ...118 ...
Page 124: ...124 ...
Page 138: ...8 9 138 Maintenance ...
Page 139: ...11 12 12 6 10 Maintenance 139 ...
Page 150: ...150 ...
Page 160: ...160 ...
Page 183: ...Technical data 183 ...
Page 184: ...184 Technical data ...
Page 189: ... Dimension drawing examples ACS880 07LC 0850A 7 Dimensions 189 ...
Page 190: ...ACS880 07LC 1660A 7 6 pulse 190 Dimensions ...
Page 191: ...ACS880 07LC 1660A 7 A004 12 pulse Dimensions 191 ...
Page 192: ...ACS880 07LC 3260A 7 192 Dimensions ...
Page 195: ... 600 mm with main breaker double busbar bottom cable entry Dimensions 195 ...
Page 197: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 197 ...
Page 198: ...Inverter module cubicle with three R8i modules bottom cable exit 198 Dimensions ...
Page 199: ...Brake chopper cubicle Dimensions 199 ...
Page 200: ...200 ...
Page 216: ... Declaration of conformity 216 The Safe torque off function ...
Page 217: ...The Safe torque off function 217 ...
Page 218: ...218 ...
Page 220: ...220 ...