Parameters 267
In ModuleBus communication, defines whether the drive is of
the “engineered” or “standard” type.
Note:
This parameter cannot be changed while the drive is
running.
ABB engineered
drive
The drive is an “engineered drive” (data sets 10…25 are
used).
0
ABB standard drive
The drive is a “standard drive” (data sets 1…4 are used).
1
Selects the DDCS channel used for connecting an external
controller (such as an AC 800M).
Not in use
None (communication disabled).
0
Slot 2A
Channel A on FDCO module in slot 2.
2
Slot 2B
Channel B on FDCO module in slot 2.
5
RDCO CH 0
Channel 0 on RDCO module (with BCU control unit only).
10
XD2D
Connector XD2D.
7
Selects the node address of the drive for communication with
the external controller. No two nodes on-line may have the
same address.
With an AC 800M (CI858) DriveBus connection, drives must
be addressed 1…24; with an AC 80 DriveBus connection,
drives must be addressed 1…12. Note that the BusManager
function must be disabled in the DriveBus controller.
With optical ModuleBus, the drive address is set according to
the position value as follows:
1. Multiply the hundreds of the position value by 16.
2. Add the tens and ones of the position value to the result.
For example, if the position value is 101, this parameter must
be set to 1×16 + 1 = 17.
1
1…254
Node address.
Selects the topology of the fiber optic link with an external
controller.
Ring
The devices are connected in a ring topology. Forwarding of
messages is enabled.
0
Star
The devices are connected in a star topology (for example,
through a branching unit). Forwarding of messages is
disabled.
1
Selects the communication speed of the channel selected by
parameter
.
1 mbps
1 megabit/second.
1
2 mbps
2 megabit/second.
2
4 mbps
4 megabit/second.
4
8 mbps
8 megabit/second.
8
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...