198 Parameters
Coast stop (Off2)
With the drive running:
• 1 = Normal operation.
• 0 = Stop by coasting. The drive can be restarted by
restoring the start interlock signal and switching the start
signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
1
Eme ramp stop
(Off3)
With the drive running:
• 1 = Normal operation
• 0 = Stop by ramping along emergency stop ramp defined
by parameter
. After the drive
has stopped, it can be restarted by removing the
emergency stop signal and switching the start signal from
0 to 1.
With the drive stopped:
• 1 = Starting allowed
• 0 = Starting not allowed
2
Selects the source of the emergency stop signal. The stop
mode is selected by parameter
0 = Emergency stop active
1 = Normal operation
Note:
This parameter cannot be changed while the drive is
running.
Active (false)
0.
0
Inactive (true)
1.
1
Reserved
2
DI1
Digital input DI1 (
, bit 0).
3
DI2
Digital input DI2 (
, bit 1).
4
DI3
Digital input DI3 (
, bit 2).
5
DI4
Digital input DI4 (
, bit 3).
6
DI5
Digital input DI5 (
, bit 4).
7
DI6
Digital input DI6 (
, bit 5).
8
Source selection (see
on page
). -
Defines the zero speed limit. The motor is stopped along a
speed ramp (when ramped stop is selected or emergency
stop time is used) until the defined zero speed limit is
reached. After the zero speed delay, the motor coasts to a
stop.
30.00 rpm
0.00…30000.00
rpm
Zero speed limit.
See par.
No.
Name/Value
Description
Def/FbEq16