20
ACS550 User’s Manual
Installation
Power connection diagrams
The following diagram shows the terminal layout for frame size R3, which, in
general, applies to frame sizes R1
…
R6, except for the R5/R6 power and ground
terminals.
WARNING!
For IT systems and corner grounded TN systems, disconnect the
internal EMC filter by removing:
- On ACS550-01: screws EM1 and EM3
- On ACS550-U1: screw EM1 (drive is shipped with EM3 already removed).
See
on page
and
on page
.
Panel connector
Fault LED (red)
Optional module 1
J2 – DIP switch
X1 – Communications
Optional module 2
GND
Power output to motor
Power input
EM1
X1 – Analog inputs and outputs
X1 – Digital inputs
X1 – Relay outputs
J2
ON
off position
on position
for RS485 termination
(and 10 V ref. voltage output)
(and 24 V aux. voltage output)
PE
(U1, V1, W1)
(U2, V2, W2)
Optional braking
Frame
size
Terminal
labels
Brake options
R1, R2 BRK+, BRK- Brake resistor
R3, R4 UDC+, UDC- • Braking unit
• Chopper and resistor
(RS485)
R5/R6 differ.
See
Frame sizes
next page.
Diagram shows the R3 frame.
J2
ON
Other frames have similar layouts.
J1
AI1: (in voltage position)
AI2: (in current position)
ON
ON
J1 – DIP switches for analog inputs (two types can be used)
ON
12
J1
FlashDrop option
Power LED (green)
3AUA0000001571
EM3
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...