268
ACS550 User’s Manual
Technical data
IT systems
WARNING!
Do not attempt to install or remove EM1, EM3, F1 or F2 screws while
power is applied to the drive’s input terminals.
For IT systems [an ungrounded power system or a high resistance-grounded (over
30 ohm) power system]:
• Disconnect the ground connection to the internal EMC filters:
– ACS550-01, frame sizes R1…R4: Remove both the EM1 and EM3 screws
(see section
).
– ACS550-U1, frame sizes R1…R4: Remove the EM1 screw –
drive is shipped
with EM3 removed (see section
on page
– Frame sizes R5…R6: Remove both the F1 and F2 screws (see section
, page
• Where EMC requirements exist, check for excessive emission propagated to
neighboring low voltage networks. In some cases, the natural suppression in
transformers and cables is sufficient. If in doubt, use a supply transformer with
static screening between the primary and secondary windings.
• Do NOT install an external RFI/EMC filter. Using an EMC filter grounds the input
power through the filter capacitors, which could be dangerous and could damage
the drive.
Drive’s power connection terminals
The following table provides specifications for the drive’s power connection
terminals.
Frame
size
U1, V1, W1
U2, V2, W2
BRK+, UDC+ terminals
Earthing PE terminal
Max. terminal size
Torque
Max. terminal size
Torque
mm
2
AWG
N·m
lb-ft
mm
2
AWG
N·m
lb-ft
R1
1
6
8
1.4
1
4
10
1.4
1
R2
1
10
6
1.4
1
10
8
1.4
1
R3
1
25
3
1.8
1.3
16
6
1.8
1.3
R4
1
50
1/0
2
1.5
35
2
2
2
R5
1
70
2/0
15
11
70
2/0
15
11
R6
185
350 MCM 40
30
95
4/0
8
6
00467918.xls B
1
Aluminium cable cannot be used with frame sizes R1…R5 because of its lower capacity.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...