ACS550 User’s Manual
229
Technical Data
Note!
The filter does not assure compliance with radiated emissions limits.
Warning! Do not use RFI/EMC filters in a floating, or impedance grounded
network.
Maximum Cable Length for EN 61800-3 CE First Environment, Unrestricted Distribution
(CISPR11 Class B) Compliance (Conducted Emissions Only)
Drive Type
Switching Frequency (Parameter 2606)
1 or 4 kHz (2606 = 1 or 4)
8 kHz (2606 = 8)
Max. Length / RFI/EMC Filter
Max. Length / RFI/EMC Filter
ACS550-x1
-03A3-4
R1
10 m (33 ft) /
ACS400-IF11-3
10 m (33 ft) /
ACS400-IF11-3
ACS550-x1
-04A1-4
ACS550-x1
-06A9-4
ACS550-x1
-08A8-4
ACS550-x1
-012A-4
ACS550-x1
-015A-4
R2
10 m (33 ft) /
ACS400-IF21-3
10 m (33 ft) /
ACS400-IF21-3
ACS550-x1
-023A-4
ACS550-x1
-031A-4
R3
10 m (33 ft) /
ACS400-IF31-3
10 m (33 ft) /
ACS400-IF31-3
ACS550-x1
-038A-4
ACS550-x1
-044A-4
R4
10 m (33 ft) /
ACS400-IF41-3
10 m (33 ft) /
ACS400-IF41-3
ACS550-x1
-059A-4
ACS550-x1
-072A-4