100
ACS550 User’s Manual
Start-Up
Group 25: Critical Speeds
This group defines up to three critical speeds or ranges of speeds that are to be
avoided due, for example, to mechanical resonance problems at certain speeds.
Code Description
2501
CRIT SPEED SEL
Sets the critical speeds function on or off. The critical speed
function avoids specific speed ranges.
0 = OFF – Disables the critical speeds function.
1 = ON – Enables the critical speeds function.
Example
: To avoid speeds at which a fan system vibrates badly:
• Determine problem speed ranges. Assume they are found to
be: 18…23 Hz and 46…52 Hz.
• Set 2501
CRIT
SPEED
SEL
= 1.
• Set 2502
CRIT
SPEED
1
LO
= 18 Hz.
• Set 2503
CRIT
SPEED
1
HI
= 23 Hz.
• Set 2504
CRIT
SPEED
2
LO
= 46 Hz.
• Set 2505
CRIT
SPEED
2
HI
= 52 Hz.
2502
CRIT SPEED 1 LO
Sets the minimum limit for critical speed range 1.
• The value must be less than or equal to 2503
CRIT
SPEED
1
HI
.
• Units are rpm, unless 9904
MOTOR
CTRL
MODE
= 3 (
SCALAR
:
SPEED
), then units are Hz.
2503
CRIT SPEED 1 HI
Sets the maximum limit for critical speed range 1.
• The value must be greater than or equal to 2502
CRIT
SPEED
1
LO
.
• Units are rpm, unless 9904
MOTOR
CTRL
MODE
= 3 (
SCALAR
:
SPEED
), then units are Hz.
2504
CRIT SPEED 2 LO
Sets the minimum limit for critical speed range 2.
• See parameter 2502.
2505
CRIT SPEED 2 HI
Sets the maximum limit for critical speed range 2.
• See parameter 2503.
2506
CRIT SPEED 3 LO
Sets the minimum limit for critical speed range 3.
• See parameter 2502.
2507
CRIT SPEED 3 HI
Sets the maximum limit for critical speed range 3.
• See parameter 2503.
f
output
52
46
23
18
f
REF
(Hz)
f1L
18
f2L
46
f1H
23
f2H
52