8
ACS255 – IP66 (600V Variants)
EASY START-UP GUIDE
Display
Keypad Operation can be found
In Section 6 and 7.2.
IMPORTANT
HARDWARE ENABLE
Link the terminals as shown
Above, optionally through switch
contacts to enable the drive
Control Terminals
Run / Stop 10K Pot
Close the switch to run (enable)
Open the switch to stop
Motor Cable
Cable size recommendation values given
on page 59.
Observe the maximum permissible motor
cable length
For Motor cable lengths > 50 metres, an
output filter is recommended
Use a screened (shielded) cable. The shield
should be bonded to earth at both ends
Motor Connection
Check for Star or Delta Connection according
to the motor voltage rating (See page 22).
Enter the Motor Nameplate Data into the
drive Parameters as follows
Motor Rated Voltage : 9905
Motor Rated Current : 9906
Motor Rated Frequency : 9907
Motor Rated Speed (Optional) : 9908
M
1
9
12 13
Fuse rating
recommendation
values given on
page 59
AC Supply Connection
500 – 600 Volts + / - 10%