8.8.1 Function
The drive is equipped with a hard-wired emer-
gency-off circuit. When an emergency situation
occurs during operation, this safety feature
ensures that the drive can be disconnected with-
out delay from the main power supply. When the
EMERGENCY OFF pushbutton has been pressed
while the drive is at standstill, the main power sup-
ply cannot be connected to the drive, hence the
drive cannot be started up.
The EMERGENCY OFF pushbutton of the drive is
part of the operator control panel
and fea-
tures a latching switch action.
—
Pressing the EMERGENCY-OFF
pushbutton does not disconnect
the auxiliary power supply from
the drive.
8.8.2 Initiating an emergency-off
To initiate an emergency-off, press the EMER-
GENCY OFF pushbutton on the control compart-
ment door or an external EMERGENCY OFF
pushbutton (if present) linked to the emergency-
off circuit.
When an emergency-off is initiated during drive
operation, the following takes place:
• The MCB opens.
• The drive coasts down.
• The DC link of the drive discharges.
• The status line of the CDP control panel alter-
nates between the message
EmergencyOff,
NotReadyOn.
•
The
EMERGENCY RESET
pushbutton flashes.
• The SUPPLY OFF pushbutton flashes.
8.8.3 Starting the drive after an emergency-off
1. To start the drive after an emergency-off refer-
ence value, unlatch the EMERGENCY OFF push-
button.
2. Turn the EMERGENCY OFF pushbutton into the
direction indicated by the arrows on the push-
button to return the pushbutton to its initial
position.
3. Press the RESET key on the CDP control panel to
cancel the emergency-off message on the dis-
play.
4. To reset the emergency-off safety relay of the
drive, press the EMERGENCY RESET pushbut-
ton.
After resetting, the status message of the drive
changes to
ReadyOn
.
The main power supply can be connected to the
drive and the drive can be started again.
1 L ->
600.0 rpm
StateINU
EmergeOff
MOTOR SP
0.00 rpm
POWER
0.0 kW
EmergencyOff
NotReadyOn
1 L ->
0.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
Summary of Contents for ACS2000 AFE 1MVA
Page 6: ...170 Replacing filter mats 171 Phase modules location 171 Phase module Dimensions and weight ...
Page 8: ...Terms trademarks related documentation ...
Page 13: ...13 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 14: ...General information on manual and drive ...
Page 19: ...19 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 20: ...Important note on main circuit breaker ...
Page 48: ...Chapter 3 Control system 49 Overview 50 Main components 54 I O interfaces ...
Page 67: ...67 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 77: ...77 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 83: ...83 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J 5 1 3 2 1 4 A B C E D ...
Page 85: ...85 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 113: ...113 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 114: ...Commissioning check list ...
Page 149: ...149 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 176: ......