Actual signals and parameters
174
16.07
PARAMETER SAVE
Saves the valid parameter values to the permanent memory.
Note:
A new parameter value of a standard macro is saved automatically when
changed from the panel but not when altered through a fieldbus connection.
DONE
Saving completed
0
SAVE..
Saving in progress
1
16.08
RUN ENA PTR
Defines the source or constant for value Par.
of parameter
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
for information on
the difference.
-
16.09
CTRL BOARD
SUPPLY
Defines the source of the control board power supply.
Note:
If an external supply is used but this parameter has value INTERNAL,
the drive trips on a fault at power switch off.
INTERNAL 24V
Internal (default).
1
EXTERNAL 24V
External. The control board is powered from an external supply.
2
16.11
FAULT RESET PTR
Defines the source or constant for selection PARAM 16.11 of parameter
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
for information on
the difference.
-
16.12
POWER ON RESET
TD
Defines the time delay for drive reset after the power on ackn (DIL) signal is
activated. Can be used for faults generated during drive initialization. See page
for a wiring diagram of the power ackn signal.
0 ... 60 s
Setting range in seconds.
0 ... 600
16.13
USER MACRO PTR
Defines the source or constant for parameter
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
EXT1 STRT PTR
for information on the difference.
-
16.14
FAN KWH CNT
RESET
Resets the cooling fan running time counter or kWh counter.
NOT SEL
No selection.
0
FAN CNT RST
Resets the running time counter of the drive cooling fan indicated by actual
signal
FAN ON-TIME.
1
KWH CNT RST
Resets the kWh counter indicated by actual signal
KILOWATT HOURS. 2
20 LIMITS
Drive operation limits.
20.01
MINIMUM SPEED
Defines the allowed minimum speed. This value is the limit the drive will use in
reverse direction. The limit cannot be set if parameter
Note:
The limit is linked to the motor nominal speed setting, that is
parameter
. If
is changed, the default speed limit will also
change.
-18000 / (no. of pole
pairs) … Par.
rpm
Minimum speed limit.
Note:
If the value is positive, the motor cannot be run in the reverse direction.
1 = 1 rpm
20.02
MAXIMUM SPEED
Defines the allowed maximum speed. This value is the limit the drive will use in
forward direction. The value cannot be set if parameter
= SCALAR.
Note:
The limit is linked to the motor nominal speed setting, that is
parameter
. If
is changed, the default speed limit will also
change.
… 18000 /
(no. of pole pairs) rpm
Maximum speed limit
1 = 1 rpm
Index
Name/Selection
Description
FbEq
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...