Actual signals and parameters
173
16.02
PARAMETER LOCK
Selects the state of the parameter lock. The lock prevents parameter changing.
OPEN
The lock is open. Parameter values can be changed.
0
LOCKED
Locked. Parameter values cannot be changed from the control panel. The lock
can be opened by entering the valid code to parameter
.
1
16.03
PASS CODE
Selects the pass code for the parameter lock (see parameter
0 … 30000
Setting 358 opens the lock. Setting 584 opens the group 99 read only lock. The
value reverts back to 0 automatically.
0 … 30000
16.04
FAULT RESET SEL
Selects the source for the fault reset signal. The signal resets the drive after a
fault trip if the cause of the fault no longer exists.
NOT SEL
Fault reset only from the control panel keypad (RESET key).
1
COMM.CW
Reset through the fieldbus Control Word (bit 7), or with the RESET key of the
control panel.
Note:
Reset through fieldbus Control Word (bit 7) is enabled automatically and
it is independent of parameter
or
is set
to COMM.CW.
2
ON STOP
Reset along with the stop signal received through a digital input, or with the
RESET key of the control panel.
3
DI8
Digital input DI8 is the signal source.
4
DI10
Digital input DI10 is the signal source.
5
DI12
Digital input DI12 is the signal source.
6
PARAM 16.11
Source selected with parameter
7
16.05
USER MACRO IO
CHG
Enables the change of the user macro through a digital input. See parameter
. The change is only allowed when the drive is stopped. During the
change, the drive does not start.
Note:
Always save the user macro with parameter
after changing any
parameter settings, or reperforming the motor identification. The last settings
you have saved are loaded into use whenever the power is switched off and on
again or the macro is changed. Any unsaved changes will be lost.
Note:
The value of this parameter is not included in the user macro. A setting
once made remains despite the user macro change.
Note:
Selection of User Macro 2 can be supervised via relay output RO3. See
parameter
RO PTR3 for more information.
NOT SEL
User macro change is not possible.
1
DI8
Digital input DI8 is the signal source.
2
DI9
Digital input DI9 is the signal source.
3
DI10
Digital input DI10 is the signal source.
4
COMM.CW
Macro change through the fieldbus Control Word (bit 12).
5
PARAM 16.13
Source selected with parameter
6
16.06
LOCAL LOCK
Disables entering local control mode (
LOC/REM
key of the panel).
WARNING!
Before activating, ensure that the control panel is not
needed for stopping the drive!
OFF
Local control allowed.
0
ON
Local control disabled.
65535
Index
Name/Selection
Description
FbEq
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...