Drive module of frame size R8
39
18
Fasten the back panel of the enclosure.
19
Fasten the side panels of the enclosure.
20
Fasten the roof plate:
1. Cut an opening to the roof
wire mesh for the upper edge
of the air baffle. Place the
mesh on the top of the
enclosure frame.
2. Fasten the enclosure roof
plate above the mesh with four
50 mm spacers at the corners.
21
Remove the vertical support rail on the hinged side of the enclosure door. See page
22
Cut openings in the door for the ventilation gratings, control panel mounting platform and other devices. Fasten and
wire the door devices. See
RPMP-11/13 Control Panel Mounting Platform Kit Installation Guide
[3AFE68400643
(English)].
Install the ventilation gratings on the door as follows:
1. Fasten the gratings (1a) and the EMC compatible fan-and-air-filter unit (1b).
2. Place the air filter mat between the lower grating and the outer louvred grating.
3. Push the louvred grating onto its place.
Step
Instruction
Photo
1
2
View of the EMC compatible
fan-and-air-filter unit on the
back side of the door
1a
1b
3
Summary of Contents for ACS 800 Series
Page 4: ......
Page 10: ...About this manual 10 ...
Page 42: ...Drive module of frame size R8 42 ...
Page 44: ...Dimensional drawings 44 Frame size R7 68469091_1 ...
Page 45: ...Dimensional drawings 45 Frame size R8 68469091_2 ...
Page 47: ...Dimensional drawings 47 Air baffle at the right hand side of the drive module 68484898 A ...
Page 48: ...Dimensional drawings 48 Air baffle at the left hand side of the drive module 68484910 A ...
Page 51: ......