Appendix A – ACS/ACC 600 Technical Data
A-16
601/604/607 US Supplement
External Control
Connections
Data of the external control connection boards of the ACx 600 product
family are given below.
ACS/ACC 600
NIOC-01 Board
Analog Inputs
The advantage of
the differential
analog input is that
the ground potential
of the device or
transmitter sending
an analog signal
can differ up to ± 15
V from the ground
potential of the
ACx 600 chassis
without disturbing
the signal.
Differential input
also efficiently
attenuates common
mode disturbances
coupled to control
cables.
ACS 600: Two Programmable Differential
Current Inputs: 0 (4) to 20 mA, R
in
= 100
Ω
ACC 600: Two Differential Current Inputs:
0 to 20 mA, R
in
= 100
Ω
ACS 600: One Programmable Differential
Voltage Input: ACS 600: 0 (2) to 10 V, R
in
>
200 k
Ω
ACC 600: One Differential Voltage Input: 0
to 10 V, R
in
> 200 k
Ω
Common Mode Voltage:
±
15 VDC, max.
Common Mode Rejection Ratio: > 60 dB at
50 Hz
Resolution: 0.1 % (10 bit)
Inaccuracy:
±
0.5% (Full Scale Range) at
25
°
C (77 °F). Temperature Coefficient:
±
100 ppm/
°
C (56 ppm/ °F), max.
Input Updating Time: 12 ms (ACS 600),
44 ms (ACC 600)
Constant Voltage
Output
Voltage: 10 VDC ± 0.5% (Full Scale Range)
at 25 °C (77 °F). Temperature Coefficient:
± 100 ppm/°C (56 ppm/ °F), max.
Maximum Load: 10 mA
Applicable Potentiometer: 1 k
Ω
to 10 k
Ω
Auxiliary Power
Output
Voltage: 24 VDC ± 10%, Short circuit proof
Maximum Current: 250 mA (130 mA with
NLMD-01 option)
Analog Outputs
ACS/ACC 600: Two Programmable Current
Outputs: 0 (4) to 20 mA, R
L
< 700
Ω
Resolution: 0.1 % (10 bit)
Inaccuracy:
±
1% (Full Scale Range) at
25
°
C. Temperature Coefficient:
±
200 ppm/
°
C (110 ppm/ °F), max.
Output Updating Time: 24 or 100 ms
(ACS 600), 44 ms (ACC 600)