Appendix A – ACS/ACC 600 Technical Data
A-10
601/604/607 US Supplement
1)
The maximum acceptable size of the cable is 3x120+70 (3x(AWG 000) + AWG 00); cross sectional areas of
copper conductors in mm
2
, 3 x phase con PE conductor). Aluminum cable cannot be connected
due to cable lug size.
2)
This is the grounding terminal for the PE bus and the frame of the ACx 604 module. The terminal is to be
connected to the PE bus of the cabinet the module is installed in. M10 metric bolt (3/8 in. dia.).
3)
Isolated Stud terminal
ACx 604/607
Type Codes
AC Line Terminals
Motor Terminals
Grounding
Terminals
Cabinet
(Frame)
U1,V1,W1
T
U2,V2,W2
T
Grounding
PE
T
Cu
Al
Lbs/
Nm
Cu
Al
Lbs/
Nm
Lbs/
Nm
ACx 604-0120-4
ACx 604-0140-4
1x(10-120)
3)
#0000
1)
22/30
1x(10-120)
#0000
1)
22/30
41 mm
2 2)
22/30
-
(R7)
ACx 604-0120-2
ACx 604-0170-4
ACx 604-0210-4
ACx 604-0260-4
1x(10-240)
3)
400MCM
1x(10-240)
3)
400MCM
22/30
3x(12-240)
3x400MCM
3x(12-240)
3x400MCM
33/44
M10 (2 pcs)
3)
22/30
-
(R8)
ACx 604-0140-2
ACx 604-0170-2
ACx 604-0320-4
ACx 604-0400-4
1x(10-240)
3)
400MCM
1x(10-240)
1)
400MCM
22/30
3x(12-240)
3x400MCM
3x(12-240)
3x400MCM
33/44
M10 (2 pcs)
2)
22/30
-
(R9)
ACx 607-0120-4
1x120
#0000
1x120
#0000
22/30
1x(12-120)
#0000
1x(12/120)
#0000
22/30
M12
22/30
MNS
(R7)
ACx 607-0140-4
1x185
350MCM
2x(12/240)
2x400MCM
22/30
1x(12-185)
350MCM
1x(12-185)
350MCM
22/30
M12
22/30
MNS
(R7)
ACS 607-0170-4
ACx 607-0210-4
ACx 607-0260-4
2x(12-185)
2x350MCM
2x(12/240)
2x400MCM
33/44
2x(12/185)
2x350MCM
2x(12/240)
2x400MCM
33/44
M12
22/30
MNS
(R8)
ACx 607-0320-4
ACx 607-0400-4
2x(12-185)
2x350MCM
2x(12/240)
2x400MCM
33/44
2x(12-185)
2x350MCM
2x(12-240)
2x400MCM
33/44
M12
22/30
MNS
(R9)
ACx 607-0490-5
4x(12-185)
4x350MCM
4x(12-240)
4x400MCM
41/55
4x(12-185)
4x350MCM
4x(12-240)
4x400MCM
41/55 M10 (2x2 pcs) 26/35
MNS
(2xR8)
ACx 607-0610-5
ACx 607-0760-5
4x(12-185)
4x350MCM
4x(12-240)
4x400MCM
41/55
4x(12-185)
4x350MCM
4x(12-240)
4x400MCM
41/55 M10 (2x2 pcs) 26/35
MNS
(2xR9)