32
Supplemental Installation Manual for ACS580-0P
ACS580-0P with Bypass
575 Volt fuses for packaged drive
Operation
This information is unique to ACS580 bypass configurations (0P+F255+G310). This
drive system uses the ACS580-01 Hand/Auto macro for run operation. See section
Control Macros, Hand/Auto Macro in the ACS580 Standard Control Program
Firmware Manual page 90 for complete information.
575 Volt
Nominal Output
Range
Base
Drive
Frame
Size
Internal Drive Fuse
Rating
Bypass Fuse Rating (only
with Type EF Electronic
Overload)*
Type code
Drive
current
Package
power
A
HP
Class
Current
rating
(amps)
Class
Current
rating
(amps)
ACS580-0P-02A7-6+F255+G310 2.7
2
R2
Class CC 15
Class J
10
ACS580-0P-03A9-6+F255+G310 3.9
3
R2
Class CC 15
Class J
10
ACS580-0P-06A1-6+F255+G310 6.1
5
R2
Class CC 15
Class J
10
ACS580-0P-09A0-6+F255+G310 9
7.5
R2
Class CC 15
Class J
15
ACS580-0P-011A-6+F255+G310 11
10
R2
Class CC 15
Class J
20
ACS580-0P-017A-6+F255+G310 17
15
R2
Class CC 30
Class J
30
ACS580-0P-022A-6+F255+G310 22
20
R3
Class T
40
Class J
40
ACS580-0P-027A-6+F255+G310 27
25
R3
Class T
40
Class J
50
ACS580-0P-032A-6+F255+G310 32
30
R3
Class T
40
Class J
50
ACS580-0P-041A-6+F255+G310 41
40
R5
Class T
50
Class J
70
ACS580-0P-052A-6+F255+G310 52
50
R5
Class T
80
Class J
80
ACS580-0P-062A-6+F255+G310 62
60
R5
Class T
80
Class J
100
ACS580-0P-077A-6+F255+G310 77
75
R5
Class T
100
Class J
125
ACS580-0P-099A-6+F255+G310 99
100
R7
Class T
150
Class J
150
ACS580-0P-125A-6+F255+G310 125
125
R7
Class T
175
Class J
200
ACS580-0P-144A-6+F255+G310 144
150
R8
Class T
200
n/a
n/a
*When G418 option is included and on all R8 and R9 drives. (See
Summary of Contents for ACS 580-OP
Page 2: ......