30
Supplemental Installation Manual for ACS580-0P
ACS580-0P with Bypass
Branch circuit protection
Input power is connected to the ACS580 through a door interlocked circuit breaker.
When connected to a 240V or 480V power source, the ACS580 with circuit breaker
is suitable for use on a circuit capable of delivering not more than 65,000 RMS
symmetrical amperes. When connected to a 600V power source, it is suitable for use
on a circuit capable of delivering not more than 10,000 RMS symmetrical amperes.
Fuses
Note:
The UL listed drive fuses in the table are provided in the purchased product.
• Replacement fuses are required to be of the same class, current rating, and
voltage rating. Fuses from other manufacturers can be used if they are 600V rated
and meet the specifications given in the table.
• Fuses with higher current rating than specified must not be used.
575 Volt
Output
Ratings
Base
Drive
Frame
Size
Terminal Wire Range
Type Code
Amps HP
Circuit
Breaker
Motor
Terminals
(Standard)
Motor
Terminals
(G418)
Ground
Lugs UL
ACS580-0P-02A7-6+F255+G310 2.7
2
R2
#14...#1/0
5.2 lbf-ft
#18...#10
3.0...4.1 lbf-ft
#14...#2
3.0...4.1 lbf-ft
#14...#2
3.3 lbf-ft
ACS580-0P-03A9-6+F255+G310 3.9
3
R2
ACS580-0P-06A1-6+F255+G310 6.1
5
R2
ACS580-0P-09A0-6+F255+G310 9
7.5 R2
ACS580-0P-011A-6+F255+G310 11
10
R2
ACS580-0P-017A-6+F255+G310 17
15
R2
ACS580-0P-022A-6+F255+G310 22
20
R3
ACS580-0P-027A-6+F255+G310 27
25
R3
ACS580-0P-032A-6+F255+G310 32
30
R3
ACS580-0P-041A-6+F255+G310 41
40
R5
#12...#2
2.9...3.3 lbf-ft
ACS580-0P-052A-6+F255+G310 52
50
R5
#8...#2/0
9.1 lbf-ft
ACS580-0P-062A-6+F255+G310 62
60
R6
ACS580-0P-077A-6+F255+G310 77
75
R6
#8...#1
4.8...6.6 lbf-ft
ACS580-0P-099A-6+F255+G310 99
100 R7
#6...#2/0
6.4...7.3 lbf-ft
#14...#2/0
4.1...10 lbf-ft
ACS580-0P-125A-6+F255+G310 125
125 R7
#4...300MCM
6.6 lbf-ft
ACS580-0P-144A-6+F255+G310 144
150 R8
#6...250MCM
22.9 lbf-ft
#6...300MCM
25 lbf-ft