Operation and reset of the module
27
Operation and reset of the module
Operation
After installation and applying power, the RBIP-01 BACnet/IP
Router Module directly starts operation. The device is designed for
permanent full-time operation, so no additional power switch
needs to be activated.
If you need to disconnect the router module from the power
supply, remove the green power connector.
Resetting the module
The module has an internal
Reset switch.
The switch offers the following
functions:
Function
Description
Reset
To reset the device, press and release the
Reset switch.
For example, if you wish to deactivate the
DHCP server after you have activated it,
perform a reset.
DHCP
To activate the DHCP server, press and hold
down the Reset switch for more than 5 seconds
but no longer than 10 seconds.