14.1.3
Error severity E4: Warnings
Table 13: Error severity E4: Warnings
Error
severity
Location Error
code
d1
d2
d3
d4
Description
Remedy
E4
bAt
(battery)
8
22
0
0
0
Empty or missing
E4
FLd
(flash-
disk)
9
19
5
0...n
0
Medium has used
80 % of its spare
capacity
E4
FLd
(flash-
disk)
53
19
5
0
0
Root partition has
15% or less free
space left
E4
iob
(I/O bus)
257
Module
number
1
Channel
number
0
Wrong measure-
ment, false tempera-
ture at the compen-
sation channel
E4
iob
(I/O bus)
258
Module
number
1
Channel
number
0
AI531: wrong meas-
urement, potential
difference is too
high;
CD522: PWM duty
cycle out of duty
area
E4
iob
(I/O bus)
260
Module
number
1
Channel
number
0
Measurement over-
flow
Check
channel
wiring and
sensor
power
supply.
E4
iob
(I/O bus)
263
Module
number
1
Channel
number
0
Measurement under-
flow at analog input
Check
channel
wiring and
sensor
power
supply.
E4
iob
(I/O bus)
266
Module
number
1
Channel
number
0
Short circuit and cut
wire or "out of range"
E4
iob
(I/O bus)
267
Module
number
1
Channel
number
0
Output/process
voltage to small/low.
E4
iob
(I/O bus)
303
Module
number
1
Channel
number
0
Short circuit at the
analog input
Check
channel
wiring
E4
iob
(I/O bus)
304
Module
number
1
Channel
number
0
Analog value over-
flow or broken wire
at an analog input.
E4
iob
(I/O bus)
530
Module
number
1
Channel
number
0
Internal fuse at 0 V
is defect. 0 V
not connected with
GND.
E4
iob
(I/O bus)
559
Module
number
1
Channel
number
0
Short circuit at the
digital output
Check
channel
wiring
Appendix
Diagnosis messages via display of the processor module > Error severity E4: Warnings
2023/03/03
3ADR011074, 1, en_US
104