14.1.2
Error severity E3: Minor errors
Table 12: Error severity E3: Minor errors
Error
severity
Location Error
code
d1
d2
d3
d4
Description
Remedy
E3
iob
(I/O bus)
3
Module
number
1
Channel
number
0
Discrepancy time
expired
Check dis-
crepancy
time value,
channel
wiring and
sensor.
E3
FLd
(flash-
disk)
10
19
5
0...n
0
Medium has almost
used its complete
spare capacity or is
already dead, action
required
E3
iob
(I/O bus)
12
Module
number
1
Channel
number
0
Test pulse error
Check
wiring and
sensor
E3
iob
(I/O bus)
13
Module
number
1
Channel
number
0
Test pulse cross-talk
error
Check
wiring and
sensor. If
this error
persists,
replace I/O
module.
Contact
ABB tech-
nical sup-
port.
E3
iob
(I/O bus)
18
Module
number
1
Channel
number
0
Test error
E3
diS
(display)
22
21
0
0
0
Error at initialization
of display
E3
iob
(I/O bus)
25
Module
number
1
Channel
number
0
Stuck-at error
Check I/O
module
wiring.
Restart I/O
module, if
needed. If
this error
persists,
replace I/O
module.
E3
iob
(I/O bus)
28
Module
number
1
Channel
number
0
Cross-talk error
Check I/O
module
wiring.
Restart I/O
module, if
needed. If
this error
persists,
replace I/O
module.
E3
CPU
44
0
7
0
0
Loading boot project
failed due to failing
load of retain data
Appendix
Diagnosis messages via display of the processor module > Error severity E3: Minor errors
2023/03/03
3ADR011074, 1, en_US
100